5. Check the default settings in the SCL Import view and change the settings ifthey are not suitable.The default settings in the SCL Import dialog should be correct in most cases.6. Click Import to import the SCD file.7. Check the IP address on the IEC 61850 subnetwork and change it if needed.When the SCD file is directly exported from PCM600, it uses the IP address ofthe PCM600 computer, not the COM600S.The communication towards the protection relays is now ready. For information onhow to finalize the single-line diagram and enable parameter setting throughCOM600S HMI, see COM600S documentation.4.6 Using the Web HMIWHMI is disabled by default, and has to be activated in the protection relayconfiguration. As secure communication is enabled by default, the WHMI must beaccessed from a Web browser using the HTTPS protocol.1. To enable the WHMI, select Main menu/Configuration/HMI/Web HMImode via the LHMI.2. Reboot the relay for the change to take effect.3. Log in with the proper user rights to use the WHMI.To establish a remote WHMI connection to the protection relay,contact the network administrator to check the company rules for IPand remote connections.Disable the Web browser proxy settings or make an exception to theproxy rules to allow the protection relay's WHMI connection, forexample, by including the relay's IP address in Internet Options/Connections/LAN Settings/Advanced/Exceptions.For more information on the WHMI, see the operation manual.4.7 Managing IED usersIED user authorization is disabled by default. IED user passwords can be changed inLHMI, WHMI and using the IED Users tool in PCM600.1MRS757810 C Section 4Setting up a projectREC615 and RER615 61Engineering Manual