For more information, see ...InstructionStepAsset registration (page 31)Perform Asset registration in the Administration page ofAurora Vision® Plant Portfolio Manager web interface.8Note: You will need the product number of the gateway.Verifying end-to-end data transfer (page 31)Verify end-to-end data transfer using the Aurora Vision®Plant Portfolio Manager web portal.9Configuring Ethernet adapter modules of the solar invertersConfigure the FENA Ethernet adapter module to enable communication with the inverter.1. Install the FENA module. See instructions in FENA Ethernet adapter module user'smanual.2. Power on the inverter.3. Set parameter 150.31 FBA B Enable = Enable.4. Configure adapter module parameters in parameter group 154 FBA B. For example,set the node address and the communication profile, typically Transparent 16-bit profile.See the example configuration in the below screen. The configuration uses a privatenetwork with IP address: 192.168.1.5 and network mask: 255.255.255.0). For moreinformation, see FENA Ethernet adapter module user's manual (3AUA0000093568[English]).5. Validate the settings with parameter 154.27 FBA B par refresh = Configure.20 Start-up