ABB i-bus ® KNXParameters236 2CDC508198D0211 Rev. A | AC/S 1.x.17.8.4 Group objectsObject function Name (can be changedseparately)Data point type(DPT)Length FlagsC R W T U IOutput: Cooling Building Protection Room setpointtemperatures9.001 2 bytes x x xOutput: Cooling Economy Room setpointtemperatures9.001 2 bytes x x xOutput: Cooling Standby Room setpointtemperatures9.001 2 bytes x x xOutput: Cooling Comfort Room setpointtemperatures9.001 2 bytes x x xOutput: Heating Comfort Room setpointtemperatures9.001 2 bytes x x xOutput: Heating Standby Room setpointtemperatures9.001 2 bytes x x xOutput: Heating Economy Room setpointtemperatures9.001 2 bytes x x xOutput: Heating Building Protection Room setpointtemperatures9.001 2 bytes x x xObject function Name (can be changed separately) Data type FlagsOutput: Cooling Building Protection Room setpoint temperatures 2 bytesDPT 9.001C, R, TThe module has this output group object if the Yes option is selected for the Cooling Building Protection parameter.Telegram value: 0...50 °COutput: Cooling Economy Room setpoint temperatures 2 bytesDPT 9.001C, R, TThe module has this output group object if the Yes option is selected for the Cooling Economy parameter.Telegram value: 0...50 °COutput: Cooling Standby Room setpoint temperatures 2 bytesDPT 9.001C, R, TThe module has this output group object if the Yes option is selected for the Cooling Standby parameter.Telegram value: 0...50 °COutput: Cooling Comfort Room setpoint temperatures 2 bytesDPT 9.001C, R, TThe module has this output group object if the Yes option is selected for the Cooling Comfort parameter.Telegram value: 0...50 °C