Section 6 Testing functionality6.1 Testing disturbance report6.1.1 IntroductionThe following sub-functions are included in the disturbance report function:• Disturbance recorder• Event list• Event recorder• Trip value recorder• IndicationsIf the disturbance report is set on, then its sub-functions are also set up and so it isnot possible to only switch these sub-functions off. The disturbance report functionis switched off (parameter Operation = Off) in PCM600 or the local HMI underMain menu/Settings/IED Settings/Monitoring/Disturbance report/1:DRPRDRE.6.1.2 Disturbance report settingsWhen the IED is in test mode, the disturbance report can be made active orinactive. If the disturbance recorder is turned on during test mode, recordings willbe made. When test mode is switched off all recordings made during the testsession are cleared.Setting OpModeTest for the control of the disturbance recorder during test modeare located on the local HMI under Main menu/Settings/IED Settings/Monitoring/Disturbance report/1:DRPRDRE.6.2 Identifying the function to test in the technicalreference manualUse the technical manual to identify function blocks, logic diagrams, input andoutput signals, setting parameters and technical data.1MRK 504 126-UEN - Section 6Testing functionality39Commissioning Manual