internal fault signals can also be checked via the LHMI in Main menu/Diagnostics/IED status/General.When a fault appears, record the fault indication message and state it whenordering service.Table 4:Warning indicationsWarning indication Additional informationWarningIEC 61850 ErrorIEC 61850 has not succeededin some actions such asreading the configuration file,startup etc.WarningDNP3 ErrorError in DNP3 communication.8.2.3 Additional indicationsThe additional indication messages do not activate internal fault or warning.The messages are listed in the LHMI menu under the event list. The signal statusdata is found under the IED status and in the internal event list.Table 5:Additional indicationsWarning indication Additional informationTime Synch Error Source of the time synchronization is lost or timesystem has made a time reset.BATTERY1 Error Auxiliary power is disconnected.Settings Changed Settings have been changed.Setting Groups Changed Setting group has been changed.8.3 Correction procedures8.3.1 Changing and setting the passwordThe password can only be set with PCM600.For more information, see PCM600 documentation.8.3.2 Identifying IED application problemsNavigate to the appropriate menu in the LHMI to identify possible problems.Section 8 1MRK 504 126-UEN -Troubleshooting88Commissioning Manual