RECOMMENDATIONS FOR DHW CONNECTIONSEssential recommendations for safety• The hot water output may reach temperatures in excess of 60°C, which can causescalding! It is therefore necessary to install a thermostatic mixing valve after theappliance.• The system must be fitted with an approved safety group, comprised of a 7 barsafety valve, a check valve and a shut-off valve.*Essential recommendations for the correct operation of the appliance• Flush the system before connecting the domestic hot water circuit. Refer to theinstallation instructions.• Make sure to install a pressure reducing valve set at 4.5 bar if the mains supplypressure is in excess of 6 bar.• It is recommended to install an expansion vessel in the DHW circuit to prevent the safetyvalve from opening constantly and reduce the water hammer effect in the system.• If the appliance is used as a domestic hot water preparation tank, a primaryexpansion vessel adapted to the boiler power/size and to the type of system mustbe fitted in the heating circuit (if there is no built-in expansion vessel, or if the built-in expansion vessel size is not sufficient).Cold waterHot waterTypical installation with internal DHW tankDescription1. Isolating valve2. Pressure reducing valve3. Check valve4. DHW expansion vessel5. Safety valve6. Drain valve7. Grounding8. Draw-off tap9. Thermostatic mixing valve1 2 31845679• Make sure to install the expansion vessel kit (accessory) provided for the Waterheater.* For UK specific requirements for the discharge from safety valves, refer to «G3 Require-ments and Guidance - UK Only» on page 34.WaterMaster 25 - 35 - 45 - 70 - 85 - 120 : A1006482 - 664Y7300 • Den38ENFRNLESITDEPLRUINSTALLATION• The safety valve kit :Primary circuit safety valve at the back of the water heater• The expansion vessel kit (mandatory accessory):A primary circuit expansion vessel MUST BE installed at the back of the water heater.