Installation Instruction6 IST5 Tower UPS 10kVA~40kVA User ManualRectifier/DischargerMain InputStatic SwitchManual BypassInverterChargerLoadBatteryBypass InputOutput SwitchFig. 2-4 Bypass mode operation diagram2.3.4 Maintenance Mode (Manual Bypass)A manual bypass switch is available to ensure continuity of supply to the critical loadwhen the UPS becomes unavailable e.g. during a maintenance procedure. (See Fig.2-5).Main InputManual BypassBatteryBypass InputOutput SwitchRectifier/Discharger InverterChargerLoadFig .2-5 Maintenance mode operation diagramDangerDuring Maintenance mode, dangerous voltages are present on the terminal of input, output andneutral, even with all the modules and the LCD turned off.2.3.5 ECO ModeTo improve system efficiency, UPS rack system works in Bypass mode at normal time,and inverter is standby. When the utility fails, the UPS transfers to Battery Mode andthe inverter powers the loads.