IST5 Tower UPS 10kVA~40kVA User Manual 15Installation Instruction3.5 Cable EntryCables can enter the UPS cabinet from the side or from the bottom. Cable entry is madepossible through a blanking plate fitted at the bottom of the equipment. The cable entryis shown in Fig.3-11.Cable connectionCable connectionFig.3-10 Cable entry3.6 Power Cables3.6.1 SpecificationsThe UPS power cables are recommended in Table 3.2.Table 3.2 Recommended cables for power cablesContents 10/15kVA 20/30kVA 40kVAMain InputMain Input Current(A) 18/28A 35/55A 70ACable Section(mm²)A 6 10 16B 6 10 16C 6 10 16N 6 10 16Main OutputMain Output Current(A) 15/23A 30/45A 60ACable Section(mm²)A 6 10 16B 6 10 16C 6 10 16N 6 10 16Bypass Input(Optional)Bypass Input Current(A) 15/23A 30/45A 60ACable Section(mm²)A 6 10 16B 6 10 16C 6 10 16N 6 10 16