Page 30Connecting DiagramFig. 8.6* Suggested minimum cable size should be used as a guideonly, refer to AS/NZS 3000 'Australia/New Zealand WiringRules" for more details.8. Wiring Serene Wall Hung Split SystemDIP Switch Settings (Indoor Board)Fig. 8.7SETTING NETADDRESS (CCM Com. Bus)ENC3+F1CODENETADDRESS0-FFACTORYSETTING0-15 16-31 32-47 48-630-F 0-F 0-F(MULTI-FUNCTIONCONTROL BOARD)REMOTE ON/OFF FUNCTIONF2FACTORYSETTING(MULTI-FUNCTIONCONTROL BOARD)REMOTESWITCHINACTIVEREMOTE SWITCH OPEN = UNIT ONREMOTE SWITCH CLOSED = UNIT OFFREMOTE SWITCH OPEN = UNIT OFFREMOTE SWITCH CLOSED = UNIT ONNOTE FOR REMOTE ON/OFF FUNCTION:• Remove jumper wire in CN46 terminal and set F2 dip switch as above in the multi-function control board to useRemote ON/OFF switch.• When the remote switch is in "OFF" mode, the unit will be off and the remote/ wired controller will not operate.If ON button is pressed via remote/wired controller - "CP" will be displayed.• When the remote switch is in "ON" mode, the unit will operate via remote/wired controller as normal.• When using remote switch, the unit will respond within 3 seconds before turning ON or OFF.OUTDOOR UNITS2(N) NPOWER SUPPLY(SUGGESTED MINIMUM*)LINDOOR UNITS2(N)1mm² INDOOR POWERSUPPLY / DATA(2 CORE + EARTH)DOUBLE INSULATED300VAC RATED MINIMUMWRC-026ASWRC-035ASWRC-052AS1.5mm² =WRC-071ASWRC-080AS2.5mm² =14/0.20 (0.44mm²)SHIELDED DATA CABLEWITH SHIELD WIRECONNECTED TO EARTHTERMINAL0