AXIS A1214 Network Door Controller KitRequirements for compliance with UL 294This section contains information and instructions required for UL compliance. To make sure theinstallation is UL compliant, follow the instructions below in addition to the general informationand instructions provided throughout this document. In cases where pieces of informationcontradict each other, the requirements for UL compliance always replace general informationand instructions.Performance levels for access controlThis section contains performance level information required for UL 294 compliance.Feature LevelDestructive attack test ISecurity IEndurance IVStandby power ISupported readers• For UL 294, compatibility with the following readers has been verified by UL:AXIS A4020-E, AXIS A4120–E and HID Signo 20.Safety instructions• Shall be installed in accordance with Article 725.121 of the National Electrical Code,ANSI/NFPA 70.• The Axis product shall be installed and serviced by a factory trained professional.• The Axis product shall be installed within the protected premises (secured area).• The Axis product shall be mounted indoors. Outdoor use has not been evaluated orapproved by UL.• All interconnecting devices shall be UL listed and Class 2 low-voltage power limited.• All power outputs are Class 2 outputs.• All wiring methods shall be performed in accordance with ANSI/NFPA70, local codes andauthorities having jurisdiction.• The wiring of the door relay is limited only inside of the protected area.• Recommend to use UL recognized grounding wire, a size of 14-16 AWG, yellow/greencolor. Crimp the cable on the non-insulated wire pressure ring terminal which is beingdelivered as a spare part of the product. Important to use proper crimping tool andtechniques to ensure the safety of product and user.5