5-435-6-6. Setting and changing compensation coefficientThis function is used to set or change the compensation coefficient which is used to multiplythe output flow rate as required.Set range: 0.10000 to 5.9999Default: 1.0000Set and change a compensation coefficient in accordance with the following procedure:Step Procedure Screen1 Enter ENGINEERING MODE in accordance with theentry into ENGINEERING MODE (see section 5-5-10. on page 5-33). Then press the or key todisplay the screen at right.12.3 %# COEFFICIENT1.00002 Press the key to move the cursor to the positionunder a desired value to be set or changed. 12.3 %# COEFFICIENT1.00003 Using the or key, change the value to the desiredone to be set. 12.3 %# COEFFICIENT1.00504 Press the key to move the cursor to the positionunder #.Press the MODE key to return to the MEASURINGMDOE and to save data.12.3 %# COEFFICIENT1.0050CAUTIONYou have only ten minutes to return to MEASURING MODE to save the new value beforethe system resets it to the previously saved value.