1100-2294 Rev 1 492103 🔒 Stop Bits Stop bits = 1 or 2 16-bit UnsignedInteger2104 🔒 Parity 0 = None, 1 = Odd, 2 = Even2105 🔒 Enable 120ohm Termination 0 = No termination, 1 = termination enabled Boolean2106 🔒 Sensor Low Alarm(PPM/PPB/VOL/LEL)Low gas alarm in display units (Local Alarm set pointsstored on controller, override sensor values)16-bit UnsignedInteger2107 🔒 Sensor High Alarm(PPM/PPB/VOL/LEL)High gas alarm in display units (Local Alarm setpoints stored on controller, override sensor values)2108 🔒 Analog output RangeSet voltage output (0=1-5V, 1=0-5V, 2=0-10V, 3=4-20mA, 4=2-10V) ( if hardware override - writeexception / read dip 2&3)2109 🔒 Analog output Zero Adjust Sets Analog output zero offset to allow outputcalibration (in DAC codes)2110 🔒 Analog output Span Adjust Sets Analog output scaling factor to allow outputcalibration (in % scaled by x10 ie 123 = 12.3%)2111 🔒 Buzzer disable 0 = Buzzer normal operation, 1 = Buzzer disabled (ifhardware override - write exception / read dip 4)Boolean2112 🔒 Relay Contact Behavior /Failsafe0 = NO relay, 1 = Failsafe relay (if hardware override -write exception / read dip 5)2113 🔒 Alarm Latching Behavior0 = Alarms automatically reset, 1 = Alarms must beacknowledged (if hardware override - write exception /read dip 6)Boolean2114 🔒 Alarm ON Delay (0-900)secondsAlarm on delay in seconds Range (0-900 secs), i.e. (0-15 mins). (if hardware override - write exception/ readdip 7)16-bit UnsignedInteger2115 🔒 Alias Text Char 1,2 Alias Characters (16 char alias string ="XXXXXXXXXXXXXXXX")2116 🔒 Alias Text Char 3,4 Alias Characters (16 char alias string ="XXXXXXXXXXXXXXXX")2117 🔒 Alias Text Char 5,6 Alias Characters (16 char alias string ="XXXXXXXXXXXXXXXX")2118 🔒 Alias Text Char 7,8 Alias Characters (16 char alias string ="XXXXXXXXXXXXXXXX")2119 🔒 Alias Text Char 9,10 Alias Characters (16 char alias string ="XXXXXXXXXXXXXXXX")2120 🔒 Alias Text Char 11,12 Alias Characters (16 char alias string ="XXXXXXXXXXXXXXXX")2121 🔒 Alias Text Char 13,14 Alias Characters (16 char alias string ="XXXXXXXXXXXXXXXX")2122 🔒 Alias Text Char 15,16 Alias Characters (16 char alias string ="XXXXXXXXXXXXXXXX")2123 🔒 Unlock code4-digit code used to unlock user settings (0000-9999),numeric, can only be read/written if system is alreadyunlocked16-bit UnsignedInteger2124 🔒 Bluetooth Passkey6-digit Bluetooth passkey (000000-999999), numeric,can only be read/written if system is unlocked,requires power cycle to take effect32-bit UnsignedInteger2125 🔒6.4.4 Integration – CalibrationHolding Register (Function 03/06 Read / Write) 🔒2200 Sensor Calibration gasapplied (PPM/PPB/VOL/LEL)Concentration of calibration gas applied duringcalibration (must be set before calibration if using gas!= sensor nominal) set to sensor nominal on reset16-bit UnsignedInteger