1100-2294 Rev 1 513102 High Alarm flag (0 or 1 =alarm) Set if high alarm is activeBoolean3103 Sensor Fault (0 or 1 = fault) Set if any fault flag is active3104 Sensor Saturation (0 or 1 =gas outside limits) Set if gas concentration exceeds full-scale range3105 Sensor Underflow (0 or 1 =gas less than zero) Set if sensor is still in warm-up stabilization period3106 Calibration Due (0 or 1 = caldue) Set if burning hours > calibration interval6.4.8 MGS Compatibility - Clear Special StatesRead / Force Coil (Function 01/05 Read / Write) 🔒4000 🔒 Mute Buzzer Sounder MuteBoolean4001 🔒 Calibration due Clear Calibration Due Flag4002 🔒not implemented - return 0on read/exception on write Reconfigure MGS6.4.9 Integration - User TasksRead / Force Coil (Function 01/05 Read / Write) 🔒4100 🔒 Restart Force application restartBoolean4101 🔒 Factory Reset Restore system settings to defaults4102 🔒 Clear last faultsClear any fault flags held in the last fault registers.Any active faults will remain set in the last faultregister4103 🔒 Acknowledge latchedalarms/faults Acknowledge latched alarms/faults4104 🔒 Mute Buzzer Mute Buzzer for 60 minutes4105 🔒 Immediate Zero Calibration Calibrate zero now4106 🔒 Immediate Span Calibration Calibrate span now4107 🔒 Auto Zero Calibration Calibrate zero after auto calibration time4108 🔒 Auto Span Calibration Calibrate span after auto calibration time4109 🔒 Clear calibration expired flag Clear calibration due flag and rest burning hours to 04110 🔒 Clear MaximumTemperature Clear Maximum Temperature4111 🔒 Clear Maximum GasConcentration Clear Maximum Gas Concentration4112 🔒 Bluetooth Enable 0 = Disable, 1 = Enable