1100-2295 Rev 0 19Some of the screens you will access will require data entry, such as the date/time setup orlocation description. These screens will appear with a character selected, as displayed below.Use the up/down Arrow keys to scroll through the characters provided for that character’s place.Use the left/right Arrow keys to move the cursor to the next character. When all characterselections for the screen are completed, press ENTER to accept the entries.4.2 Controller Setup4.2.1 Setup ParametersBefore using the controller various parameters must be set by the user based on how thecontroller has been wired. These parameters are accessed from the main menu by selecting”CONTRLR CONFIG”.4.2.2 Relay SetupFrom the RELAY menu, each of the three relays can be configured for either normal or failsafeoperation. The default is normal, meaning normally open contacts will close with the eventcorresponding the relay designation. If fail safe is selected the relay will be normally energizedand will be de-energized with the relays designated event or a power failure.