1100-2295 Rev 0 244.3 Channel Summary and SetupPressing a CHx key from the main screen will bring up a channel summary screen with detailedinformation collected from the gas detector assigned to that channel.4.3.1 Channel Setup OverviewPrior to setting channel parameters, the installer should verify and record the instrument type,node address and baud rate for each connected detector. All detectors must be set for the samebaud rate, either 9600 (default) or 19200, and must have a unique node address. The MASTERBAUD setting in the MODBUS CONFIG menu must match the settings of the detectors. Thechannel setup screen may be accessed either by selecting CHANNEL CONFIG from the mainmenu or by pressing the channel number key twice at the main screen. For each detectorchannel there are 4 parameters the user set MON, TYP, ADR, LOC.