INTRODUCTIONI-E96-624A D - 1APPENDIX D - TERMINATION MODULECONFIGURATION (NICL01)INTRODUCTIONThe INLIM03 can use the NICL01 for termination. Table D-1lists the terminal assignments for the loop input/output con-nections. Table D-2 provides jumper settings associated withcable type. Figure D-1 shows twinax cable connections forNICL01.NOTE: Twinax cables connect to the terminals. Coax cables con-nect to the BNC connectors.CAUTION Ensure that the end marked J1 is connected to P1 on theNICL01, and J2 is connected to the LIM. Failure to do so couldresult in module damage (see Figure D-1).ATTENTION S'assuree que L'extremite identifiee par J1 est reliee a P1 dumodule NICL01 et que J2 est reliee au module LIM. Sinon, lesmodules pouiraient etre endommages (voir la figure D-1).Table D-1. NICL01 Terminal AssignmentsTB1Terminal Assignments TB2Terminal Assignments TB3Terminal Assignments123GroundCommon+24 VDC4567891011Power SystemStatus 1Power SystemStatus 2Loop 2 In, +Loop 2 In, -Loop 2, ShieldLoop 2 Out, +Loop 2 Out, -Loop 2 Out, Shield2526272829303132Loop 1 Out, ShieldLoop 1 Out, -Loop 1 Out, +Loop 1 In, ShieldLoop 1 In, -Loop 1 In, +no connectionno connectionTable D-2. BNC AssignmentsBNC Number AssignmentsJ1J2J8J9Loop 1 InLoop 1 OutLoop 2 InLoop 2 Out