© 2017 Baker Hughes, a GE company, LLC. All rights reserved.94 | BHGECalibrationNOTE Always perform configuration before running calibrationfunctions.CAUTION Pilot Trim Valve Applications require the use of the Manual Stopcalibration procedure. Do not run Find Stops or the ValVue SetupWizard on valves with Pilot Trim or damage to the valve will occur.Calibrating the SVI II AP Unit Using PushbuttonsTo calibrate the SVI II AP (see Figure 41 on page 97):1. Observe the display following power-up. The SVI II AP powers up in the previously activemode either MANUAL or NORMAL (operating) mode: