18WARNING! The signalinput must be isolatedfrom the AC line. Earth groundingsignal connections will damage thedrive and void the warranty. It isrecommended that the ID5SI-1Signal Isolator and Run/Fault Relaybe installed when using signalfollowing.Catalog Nos. ID5401-CO, ID5402-CO, ID5403-CO, ID5405-CO: TheID5SI-1 is factory calibrated for 0 to±5 Volt DC signal input. Connect thevoltage (0 to ±25 Volt DC) or current(4 – 20 mA DC) signal input toTerminals “SIG1” (+) and “COM1” (–)of Terminal Block TB1 on theID5SI-1. For voltage following, besure Jumper J1 (on the ID5SI-1) is setto the “VOLT” position (factory set-ting). For current following, setJumper J1 (on the ID5SI-1) to the“CUR” position. See Figures 11 and12. A jumper must be installedbetween Terminals “0V” and “FWD”,of Terminal Block TB1, in order forthe drive to operate.Application Note: In theVoltage Following Mode, theinput will accept a “+” and “–“input voltage, which will run themotor in the forward andreverse direction.Notes: 1. The MIN Trimpoton Catalog Nos. ID5401-CO,ID5402-CO, ID5403-CO,ID5405-CO is not functional.Use the OFFSET Trimpot on the ID5SI-1 to offset the signal input, as described inSection 7.1, on page 22. 2. Do not use the MAX Trimpot on Catalog Nos. ID5401-CO,ID5402-CO, ID5403-CO, ID5405-CO. Use the MAX Trimpot on the ID5SI-1 to scale thesignal input, as described in Section 7.2, on page 23.5.6 Manual Start Switch Connection (CON1): The Manual Start Mode is used to manuallystart the drive or restart the drive (reset) if a fault has occurred. To operate the drive in theManual Start Mode, remove the factory installed jumper on CON1 and install the 2-wireconnector (supplied). CON1 is located on the lower PC board. Connect CON1 to amomentary switch or contact, as shown in Figure 13.REV-5VTB1+5V 0V FWD SIG1 COM1Jumper0 to ±2.5 thru 0 to ±25Volts DC+ V -CUR VOLT J1ID5SI-1TERMINALBLOCKFIGURE 11 – CATALOG NOS. ID5401-CO,ID5402-CO ID5403-CO, ID5405-COVOLTAGE FOLLOWING SIGNAL INPUT CONNECTION(0 to ±25 Volts DC)(Jumper J1 Installed in “VOLT” Position)REV-5VTB1+5V 0V FWD SIG1 COM1Jumper + -4 - 20 mA DCCUR VOLT J1ID5SI-1TERMINALBLOCKFIGURE 12 – CATALOG NOS. ID5401-CO,ID5402-CO ID5403-CO, ID5405-COCURRENT FOLLOWING SIGNAL INPUT CONNECTION(Jumper J1 Installed in “CUR” Position)FIGURE 13 – MANUAL START SWITCH CONNECTIONJumper RemovedConnector Installed forManual Start SwitchCON1A/MManual Start Switch(Momentary Contacts)(Push to Run)WhiteBlackCON1