Manual 2100-703Page 31 of 40TABLE 12Cooling Pressure – Balanced Climate AirflowAir Temperature Entering Outdoor Coil °FLow side pressure ± 4 PSIGHigh side pressure ± 10 PSIGTables are based upon Balanced Climate CFM (airflow) across the evaporator coil. If there is any doubt as to correctoperating charge being in the system, the charge should be removed and system evacuated and recharged to serial platecharge weight.NOTE: Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated checkcondenser fan wiring. See “Condenser Fan Operation”.* Operating at these conditions would be outside the compressor operating envelope and is not recommended.Model Return Air Temp(DB/WB) Pressure 75 80 85 90 95 100 105 110 115 120 125 131W18HB75/62 Low SideHigh Side11328511930812333112735513138013440513643113845713948414051214054014057480/67 Low SideHigh Side12129212731613234013636514039014341614544214746914949715052515055314958985/72 Low SideHigh Side125302131327136352141377145403148430151458153486154514155543155573155609W24HB75/62 Low SideHigh Side11629411831412133612335912538212740612943113145713348413451213654113857780/67 Low SideHigh Side12430112632312934513136813439213641713844214046914249714452514555514759285/72 Low SideHigh Side128312131334133357136381138405141431143458145486147514149544151574153612W30HB75/62 Low SideHigh Side12530812732712934813137013339513542013744713847614050714253914457314661580/67 Low SideHigh Side13431613633613835714038014240514443114645914848915052015255315458715663185/72 Low SideHigh Side139327141348143370145393147419149446151475153506155538157572159608 --*W36HB75/62 Low SideHigh Side12231212433512635812838112940513142913345413447913650413753013855614058880/67 Low SideHigh Side13132013334313536713739113841514044014246514449114551714754414857015060385/72 Low SideHigh Side135331137355139380141405143430145456147482149508150535152563153590155624