Manual 2100-587JPage 6 of 59AIR CONDITIONING MODULE OPTIONSSTD = Standard equipment CCM Compressor control module has adjustable 30 second to 5 minute delay-on-break timer. On initialpower up, or any time the power is interrupted, the delay-on-make will be 2 minutes plus 10% ofthe delay-on-break setting. There is no delay-on-make during routine operation of the unit. Themodule also provides the lockout feature (with 1 retry) for high and/or low pressure controls, and a2 minute timed bypass for low pressure control. HPC High pressure control is auto reset. Always used with compressor control module (CCM) which isincluded. See note . LPC Low pressure control is auto reset. Always used with compressor control module (CCM) which isincluded. See note . LAC Low ambient control permits cooling operation down to 0°F.CAUTIONDuring the initial firing of the burners there will probably be some amount of smoke issued to thecirculating air stream as the result of residual oil burning off of the heat exchanger tubes. This oilis required during the forming process of the stainless steel heat exchanger tubes to facilitate thebending. OSHA or the National Toxicology Program does not list the oil as a carcinogen. In vaporform this may be irritating to the eyes or could cause headaches. This is a one-time occurrence, andventilation of the space may be required depending upon the space being conditioned.CCM HPC LPC LACFactory InstalledCodeField InstalledPartSTD STD STD X N/ASTD STD STD -- H CMA-28