5H1 H2P 1 P 2F2F1Control Voltage Wiring1. A knockout is also provided in the back of the unit for control wiring. This knockout is sized for 1/2" conduit. (see Figure 13)2. Thermostat wire shall be as follows:a. Line voltage control models: Use NEC Class 1, 600V, 90˚C, AWG #10 wire with copper conductor or same gauge wire assupply line.b. 24 volt control models: Use NEC Class 1, 600V, 90˚C, AWG #18 wire with copper conductor.3. Install unit wall thermostats in accordance with the installation instructions supplied with the thermostat.NOTE: Do not locate thermostat in an area exposed to unusual temperature conditions or poor air circulation.NOTE: a. Line voltage control models of 3.3KW and 5.0KW ratings that are 208 and 240 volt, wired for 3-phase operation, should notbe used with a wall thermostat. This applies to the following models:CEH-003-M CEH-003-P CEH-005-M CEH-005-PThese models come factory wired for single phase. When these models are converted in the field to 3-phase, DO NOT USE A WALL MOUNTEDTHERMOSTAT. Thermostat control for 3-phase hookup should be provided by a CEK-TB2 (built-in thermostat).b.When using model number CEH-005-M wired single phase (factory wired) use the following thermostats:Wall Mount – C611-25,Built-In – CEK-TB2 (two-stage thermostat)4. Connect the thermostat wires to terminals H1 and P1 as shown in Figure 13. On 208 and 240 volt, single-phasemodels with line voltage control, install jumpers as shown in Figure 13.Figure 13. Thermostat wiring connectionsFigure 14.Manual reset limitA manual reset thermal limit isfactory installed on all models.The limit is located on the front ofthe heater. The manual reset limitwill not reset until the button ispushed. (208/240V line voltagecontrol heaters use two manualreset limits)FRONTBACK FRONTLine VoltageControl Models(Singe Phase):Install jumpersbetween H1 and H2and P1 and P2 on208/240V units(note dashed lines).Manual Reset LimitHeater ElementsControl Terminal BoardConnect ThermostatWires To P1 and H1To ThermostatWiring InstructionsBLACKREDREDBLACKELEMENT1ELEMENT2ELEMENT3ORANGEORANGEREDLIMITSWITCHESFANMOTORTERMINAL BLOCK FUSES*HEAT RECOVERYTHERMOSTATFAN SWITCH(BUILT-INOR REMOTE)TWO-STAGETHERMOSTATJUNCTION BLOCKGROUNDTERMINAL BOARDH1 H2 F2P1 P2 F1S1 S2 S3L1 L2 L3NOTE: ELEMENT 3 AT BACK OF HEATERMAX AMPSSUPPLYWIREGAUGE(AUG)CuCOND AlCOND#14#12#10#8#6#4#3#2#1#0121624324456687688100—122024324452606880NOTE: DENOTES OPTIONAL EQUIPMENTREPRESENTS 3-PHASE WIRING CONNECTIONS(Factory wired for single phase operation)*May not be used with built-in thermostatControl circuit wiring must beNEC Class 1 600 Volt CopperConductor and 90˚C Insulation.NOTE: For single phase operation, leads L2 and S2should be well insulated and left unconnected.POWER DISCONNECT SWITCH(Not available in Canada)[For use with CU conductors only][For use with CU or AL conductors]Use 75˚C field supply wireWIRING DIAGRAM #13.3 & 5 KW, 208/240V, 1-3 Phase w/Line Voltage ControlBASIC MODELS:CEH-003-M, CEH-003-P, CEH-005-M, CEH-005-PNOTE: Single pole thermostat may be usedif H1 and H2 are connected with a jumperand P1 and P2 are connected with a jumper.FAN RELAYUse H1 and P1 as primaryand H2-P2 as secondaryfor proper heater operation.Two stage is required forthree-phase operation.1 3H HWiring Diagrams