Table 19 -- DRIVE Status IndicatorSTATEOffFlashingRedSolidRedOrangeFlashingGreenCAUSEThe Gateway is notpowered or is not con-nected properly to thedrive.The Gateway is notreceiving a ping mes-sage from the drive.The drive has refusedan I/O connection fromthe Gateway.The Gateway is con-nected to a product thatdoes not support Rock-well Automation DPIcommunications.The Gateway is estab-lishing an I/O connec-tion to the drive or theI/O has been disabled.The Gateway is prop-erly connected and iscommunicating with thedrive.CORRECTIVE ACTION• Securely connect theGateway to the drive usingthe DPI ribbon cable.• Apply power to the drive.• Verify that cables aresecurely connected.• Cycle power to the drive.IMPORTANT: Cycle powerafter making the followingcorrection:• Verify that all DPI cableson the drive are securelyconnected and not dam-aged. Replace cables ifnecessary.• Check wires leading to theA32 terminal block.• Check that A32 terminalblock is fully engaged.Normal behavior.Solid No action required.GreenMS STATUS INDICATOR -- The MS status indicator is thesecond LED from the fight of the Gateway. See Table 20.Table 20 -- MS Status Indicator: State DefinitionsSTATE CAUSEOff The Gateway is not)owered.FlashingGreenSolidRedThe Gateway is opera-tional. No I/O data isbeing transferred.The Gateway is opera-tional and transferringI/O data.CORRECTIVE ACTION• Securely connect theGateway to the drive usingthe ribbon cable.• Apply power to the drive.Normal behavior during SICconfiguration initialization3rocess.No action required.NET A STATUS INDICATOR -- The NET A status indica-tor is tile third LED from the right of the Gateway. SeeTable 21.Table 21 -- NET A Status Indicator:State DefinitionsSTATE CAUSE CORRECTIVE ACTIONOff The module is not pow- • Securely connect theered or is not properly Gateway ribbon cable toconnected to the the drive DPI board.network. • Attach the RS485 cable inFirst incoming network Gateway to the connector.command not yet rec- • Apply power to the drive.ognized.Flashing Online to network, but No action required. The LEDGreen not producing or con- will turn solid green whensuming I/O information, communication resumes.Solid The module is properly No action required.Green connected and commu-nicating on the network.NET B STATUS INDICATOR -- Tile NETB status indicatoris the left LED on file Gateway. See Table 22.Table 22 -- NET B Status Indicator:State DefinitionsSTATE CAUSE CORRECTIVE ACTIONOff Gateway not receiving • Check wires leading todata over the network. A32 terminal block.• Check that A32 terminalblock is fully engaged.Solid Gateway is transmit- No action required.Green ting data.Physical Data -- Tables 23A-29 and Fig. 48-57 provideadditional information on component weights, compressor fitsand clearances, physical and electrical &Lta, and wiring sche-matics for the operator's convenience during troubleshooting.Do not attempt to disconnect flanges while the machine isunder pressure. Failure to relieve pressure can result in per-somd injury or damage to the unit.Before rigging the compressor, disconnect all wires enter-ing the power panel.100