Table 4 -- ICVC Display Data (cont)EXAMPLE 18 -- SETUP1 DISPLAY SCREENTo access this display from the ICVC default screen:1. Press _MENU_.2. Press _.3. Scroll down to highlight [EQUIPMENT SERVICE I .4. Press _SELECTI.5. Scroll down to highlight ISEf0P1].6. Press [SE_].DESCRIPTIONComp Motor Temp OverrideCond Press OverrideRectifier Temp OverrideInverter Temp OverrideComp Discharge AlertComp Thrust Brg AlertChilled MediumChilled Water DeadbandEvap Refrig TrippointRefrig Override Delta TEvap Approach AlertCond Approach AlertCondenser Freeze PointFlow Delta P DisplayEvap Flow Delta P CutoutCond Flow Delta P CutoutWater Flow Verify TimeOil Press Verify TimeRecycle ControlRestart Delta TShutdown Delta TSpare Alert/Alarm EnableDisable=0, Lo=1/3,Hi=2/4Spare Temp #1 EnableSpare Temp #1 LimitSpare Temp #2 EnableSpare Temp #2 LimitSTATUS150-20090-165155-170155-170125-200165-1850/10.5-2.00.0-40.02.0-5.00.5-150.5-15-20 - 350-10.5 - 50.00.5 - 50.00.5-5UNITSDEG FPSIDEG FDEG FDEG FDEG FWATER/BRINE^FDEG F^F^F^FDEG FDSABLE/ENABLEPSIPSIMINPOINTMT_OVERCP OVERREC OVERINV -OVERCD _,LERTTB ALERTMEDIUMCWDBERT TRIPREF OVEREVAP ALCONE) ALCDFRt_EZEFLOWDISPEVAP CUTCONE) CUTWFLO_/ T15-300 SEC2.0-10.0 DEG F0.5-4.0 DEG F0-4-40-245 DEG F0-4-40-245 DEG FOILPR Trcycr dtrcycs dtsplenspllimsp2_ensp21imNOTE: No variables are available for CCN read operation. Forcing shall not be supported on service screens.EXAMPLE 19 -- SETUP2 DISPLAY SCREENTo access this display from the ICVC default screen:1. Press [MENU].2. Press _.3. Scroll down to highlight [EQUIPMENT SERVICE].4. Press _SE[EC_.5. Scroll down to highlight ISETUP2].6. Press FSELEC_.DESCRIPTIONCapacity ControlProportional Inc BandProportional DEC BandProportional ECW BandGuide Vane Travel LimitDiffuser ControlDiffuser OptionGuide Vane 25% Load PtDiffuser 25% Load PointGuide Vane 50% Load PtDiffuser 50% Load PointGuide Vane 75% Load PtDiffuser 75% Load PointDiffuser Full Span mAVFD Speed ControlVFD GainVFD Increase StepVFD Minimum SpeedVFD Maximum SpeedDEFAULT20O125160160200175WATER1.03335634DSABLE5.05.054O02450245STATUS UNITS POINT DEFAULT%DSABLE/ENABLE%%%%%%mAgv_incgv_decgw_ecwgv_ctrldiff_optgv25df 25gv 50df 50gv_75df 75diff mavfd gainvfd stepvfd minvfd_max2-I02-I0I-330- I O00/10-780-1000-780-10o0-780-10o15-220.1-1.51-565-10090-100%%%NOTE: No variables are available for CCN read or write operation; forcing shall not be supported on service screens.6.56.028ODSABLE2505O0750180.7527O10032