18FINAL CHECKSIMPORTANT: Before leaving job, be sure to do the following:1. Ensure that all wiring is routed away from tubing andsheet metal edges to prevent rub--through or wirepinching.2. Ensure that all wiring and tubing is secure in unit beforeadding panels and covers. Securely fasten all panels andcovers.3. Tighten service valve stem caps to 1/12--turn past fingertight.4. Leave Users Manual with owner. Explain systemoperation and periodic maintenance requirements outlinedin manual.5. Fill out Dealer Installation Checklist and place in customerfile.CARE AND MAINTENANCEFor continuing high performance and to minimize possibleequipment failure, periodic maintenance must be performed onthis equipment.Frequency of maintenance may vary depending upon geographicareas, such as coastal applications. See Users Manual forinformation.PURON (R--410A) REFRIGERANT QUICK REFERENCE GUIDES Puron refrigerant operates at 50---70 percent higher pressures than R ---22. Be sure that servicing equipment and replacementcomponents are designed to operate with Puron refrigerant.S Puron refrigerant cylinders are rose colored.S Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.S Puron refrigerant systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hwhen charging into suction line with compressor operatingS Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low ---side retard.S Use hoses with 700 psig service pressure rating.S Leak detectors should be designed to detect HFC refrigerant.S Puron refrigerant, as with other HFCs, is only compatible with POE oils.S Vacuum pumps will not remove moisture from oil.S Do not use liquid ---line filter driers with rated working pressures less than 600 psig.S Do not leave Puron refrigerant suction line filter driers in line longer than 72 hours.S Do not install a suction ---line filter drier in liquid line.S POE oils absorb moisture rapidly. Do not expose oil to atmosphere.S POE oils may cause damage to certain plastics and roofing materials.S Wrap all filter driers and service valves with wet cloth when brazing.S A factory approved liquid ---line filter drier is required on every unit.S Do NOT use an R ---22 TXV.S If indoor unit is equipped with an R ---22 TXV or piston metering device, it must be changed to a hard shutoff Puron TXV.S Never open system to atmosphere while it is under a vacuum.S When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filterdriers. Evacuate to 500 microns prior to recharging.S Do not vent Puron refrigerant into the atmosphere.S Do not use capillary tube coils.S Observe all warnings, cautions, and bold text.S All indoor coils must be installed with a hard shutoff Puron TXV metering device.Copyright 2006 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.Catalog No: 25HPA--2SIReplaces: 25HPA--1SIPrinted in U.S.A. Edition Date: 03/0625HPA