185.6 - Electrical data for the hydronic moduleThe pumps fitted to these units have motors which meet efficiency class IE2 for motors < 7.5kW and IE3 for motors > 7.5kW.The additional electrical data required (1) is as follows:For the low-pressure single pump motors of 30RBM/RBP 160-520 units (option 116T)No.(2) Description(3) Units 30RBM/30RBP160 180 200 220 260 300 330 360 400 430 470 5201 Nominal efficiency at full load and nominal voltage % 85,7 85,7 85,7 85,7 85,7 87,5 87,5 87,5 89,9 89,9 89,9 891 Nominal efficiency at 75% of full load and nominal voltage % 86,9 86,9 86,9 86,9 86,9 88,2 88,2 88,2 90,4 90,4 90,4 901 Nominal efficiency at 50% of full load and nominal voltage % 86,4 86,4 86,4 86,4 86,4 87,5 87,5 87,5 89,6 89,6 89,6 89,72 Efficiency level - IE33 Year of manufacture - This information varies depending on the manufacturer and model at the time ofincorporation. Please refer to the motor nameplates.4 Company name or trademark, commercial registration number andhead office of manufacturer- Same as above5 Product model number - Same as above6 Number of motor poles - 2 2 2 2 2 2 2 2 2 2 2 27-1 Nominal shaft power output at full load and nominal voltage (400 V) kW 2,2 2,2 2,2 2,2 2,2 3 3 3 4 4 4 5,57-2 Maximum input power (400 V)(4) kW 2,80 2,80 2,80 2,80 2,80 3,81 3,81 3,81 4,96 4,96 4,96 6,808 Nominal input frequency Hz 50 50 50 50 50 50 50 50 50 50 50 509-1 Nominal voltage V 3 X 4009-2 Maximum current drawn (400 V)(5) A 4,92 4,92 4,92 4,92 4,92 6,81 6,81 6,81 8,27 8,27 8,27 11,3010 Nominal speed rps - rpm 48 - 290011 Product disassembly, recycling or disposal at end of life - Disassembly using standard tools. Disposal and recycling using an appropriate company.12 Operating conditions for which the motor is specifically designedI - Altitudes above sea level m < 1000 (6)II - Ambient air temperature °C < 40IV - Maximum operating temperature °C Please refer to the operating conditions given in this manual or in the specificconditions in the Carrier selection programs.V - Potentially explosive atmospheres - Non ATEX environment(1) Required by regulation No. 640/2009 concerning the application of directive 2005/32/EC on the eco-design requirements for electric motors.(2) Item number imposed by regulation No. 640/2009, annex I2b.(3) Description given by regulation No. 640/2009, annex I2b.(4) To obtain the maximum input power for a unit with hydronic module, add the maximum unit input power from the electrical data table to the pump power input.(5) To obtain the maximum unit operating current draw for a unit with hydronic module, add the maximum unit current draw from the electrical data table to the pump current draw.(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.For the low-pressure dual pump motors of 30RBM/RBP 160-520 units (option 116T)No.(2) Description(3) Units 30RBM/30RBP160 180 200 220 260 300 330 360 400 430 470 5201 Nominal efficiency at full load and nominal voltage % 84,9 84,9 85,7 85,7 87,5 87,5 87,5 87,5 89,9 89,9 89,9 891 Nominal efficiency at 75% of full load and nominal voltage % 86,4 86,4 86,9 86,9 88,2 88,2 88,2 88,2 90,4 90,4 90,4 901 Nominal efficiency at 50% of full load and nominal voltage % 85,9 85,9 86,4 86,4 87,5 87,5 87,5 87,5 89,6 89,6 89,6 89,72 Efficiency level - IE33 Year of manufacture - This information varies depending on the manufacturer and model at the time ofincorporation. Please refer to the motor nameplates.4 Company name or trademark, commercial registration number andhead office of manufacturer- Same as above5 Product model number - Same as above6 Number of motor poles - 2 2 2 2 2 2 2 2 2 2 2 27-1 Nominal shaft power output at full load and nominal voltage (400 V) kW 1,5 1,5 2,2 2,2 3 3 3 3 4 4 4 5,57-2 Maximum input power (400 V) (4) kW 1,94 1,94 2,80 2,80 3,81 3,81 3,81 3,81 4,96 4,96 4,96 6,808 Nominal input frequency Hz 50 50 50 50 50 50 50 50 50 50 50 509-1 Nominal voltage V 3 X 4009-2 Maximum current drawn (400 V) (5) A 3,41 3,41 4,92 4,92 6,81 6,81 6,81 6,81 8,27 8,27 8,27 11,3010 Nominal speed rps - rpm 48 - 290011 Product disassembly, recycling or disposal at end of life - Disassembly using standard tools. Disposal and recycling using an appropriatecompany.12 Operating conditions for which the motor is specifically designedI - Altitudes above sea level m < 1000(6)II - Ambient air temperature °C < 40III - Maximum operating temperature °C Please refer to the operating conditions given in this manual or in the specificconditions in the Carrier selection programs.V - Potentially explosive atmospheres - Non ATEX environment(1) Required by regulation No. 640/2009 concerning the application of directive 2005/32/EC on the eco-design requirements for electric motors.(2) Item number imposed by regulation No. 640/2009, annex I2b.(3) Description given by regulation No. 640/2009, annex I2b.(4) To obtain the maximum input power for a unit with hydronic module, add the maximum unit input power from the electrical data table to the pump power input.(5) To obtain the maximum unit operating current draw for a unit with hydronic module, add the maximum unit current draw from the electrical data table to the pump current draw.(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.