19For the high-pressure single and dual-pump motors of 30RBM/RBP 160-520 units (options 116R, 116S, 116V, 116W)No.(2) Description(3) Units 30RBM/30RBP160 180 200 220 260 300 330 360 400 430 470 5201 Nominal efficiency at full load and nominal voltage % 87,5 87,5 87,5 87,5 89,9 89,9 89 89 89 89,6 89,6 89,61 Nominal efficiency at 75% of full load and nominal voltage % 88,2 88,2 88,2 88,2 90,4 90,4 90 90 90 90,8 90,8 90,81 Nominal efficiency at 50% of full load and nominal voltage % 87,5 87,5 87,5 87,5 89,6 89,6 89,7 89,7 89,7 90,8 90,8 90,82 Efficiency level - IE33 Year of manufacture - This information varies depending on the manufacturer and model at the time ofincorporation. Please refer to the motor nameplates.4 Company name or trademark, commercial registration number andhead office of manufacturer- Same as above5 Product model number - Same as above6 Number of motor poles - 2 2 2 2 2 2 2 2 2 2 2 27-1 Nominal shaft power output at full load and nominal voltage (400 V) kW 3 3 3 3 4 4 5,5 5,5 5,5 7,5 7,5 7,57-2 Maximum input power (400 V) (4) kW 3,81 3,81 3,81 3,81 4,96 4,96 6,80 6,80 6,80 9,16 9,16 9,168 Nominal input frequency Hz 50 50 50 50 50 50 50 50 50 50 50 509-1 Nominal voltage V 3 X 4009-2 Maximum current drawn (400 V)(5) A 6,81 6,81 6,81 6,81 8,27 8,27 11,30 11,30 11,30 15,30 15,30 15,3010 Nominal speed rps - rpm 48 - 290011 Product disassembly, recycling or disposal at end of life - Disassembly using standard tools. Disposal and recycling using an appropriate company.12 Operating conditions for which the motor is specifically designedI - Altitudes above sea level m < 1000 (6)II - Ambient air temperature °C < 40III - Maximum operating temperature °C "Please refer to the operating conditions given in this manual or in the specificconditions in the Carrier selection programs."V - Potentially explosive atmospheres - Non ATEX environment(1) Required by regulation No. 640/2009 concerning the application of directive 2005/32/EC on the eco-design requirements for electric motors.(2) Item number imposed by regulation No. 640/2009, annex I2b.(3) Description given by regulation No. 640/2009, annex I2b.(4) To obtain the maximum input power for a unit with hydronic module, add the maximum unit input power from the electrical data table to the pump power input.(5) To obtain the maximum unit operating current draw for a unit with hydronic module, add the maximum unit current draw from the electrical data table to the pump current draw.(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.5.7 - Electrical data notes for the compressorsCp I Nom I MaxUnI MaxUn-10 %LRAUnCosinusPhi Max00PSG001961100A 30 41 44 215 0,8900PSG001748000A 37 50 54 260 0,89Cp CompressorI Nom Nominal current draw (A) at standardised Eurovent equivalent conditions (see definition of conditions under nominal unit current draw)I Max Maximum operating current (A)LRA Locked rotor current (A)Cos phi Max @I Max5.8 - Distribution of compressors per circuitCp Circuit 160 180 200 220 260 300 330 360 400 430 470 52000PSG001961100A A 1 - - 2 - - - 3 - 3 - -B 2 2 - 2 - 3 - - - - - -00PSG001748000A A - 1 1 - 2 2 2 - 3 - 3 4B - - 2 - 2 - 3 3 3 4 4 4Cp CompressorI Nom Nominal current draw (A) at standardised Eurovent equivalent conditions (see definition of conditions under nominal unit current draw)I Max Maximum operating current (A)LRA Locked rotor current (A)Cos phi Max @I Max