156.2 - Detailed menu descriptionIcon Displayed text* Description Associated tableGeneral Parameters General parameters GENUNITTemperatures Temperatures TEMPPressures Pressures PRESSUREInputs Status Inputs status INPUTSOutputs Status Outputs status OUTPUTSPump Status Pump status PUMPSTATRun Times Run times RUNTIMEModes Modes MODESReclaim Reclaim RECLAIMFreecooling Free cooling FREECOOLSetpoint Table Setpoint table SETPOINTTrendings Trendings TRENDINGConfiguration Menu Configuration menu CONFIG* Depends on the selected language (English by default).GENUNIT – General parametersNo. Status Unit Displayed text* Description1 0 to 3 - Local=0 Net.=1 Remote=2 Operating mode:0 = Local1 = Network2 = Remote2 - - Run Status Unit running status: Off, Stopping, Delay,Running, Ready, Override, Tripout, Test, Runtest3 0 to 1 - Net.: Cmd Start/Stop Unit start/stop via Network4 0 to 1 - Net.: Cmd Occupied Unit time schedule via Network5 - min Minutes Left for Start Minutes before the unit start-up6 - - Heat/Cool status Heating/cooling status7 0 to 2 - Heat/Cool Select Heating/cooling selection8 - - 0=Cool. 1=Heat. 2=Auto 0 = Cooling1 = Heating2 = Automatic heating/cooling control9 0 to 2 - Setpoint Select Setpoint selection10 - - 0=Auto. 1=Spt1. 2=Spt2 0 = Automatic setpoint selection1 = Setpoint 12 = Setpoint 211 0 to 1 - Setpoint Occupied? Setpoint status12 0 to 100 % Percent Total Capacity Total unit capacity13 - A Actual Chiller Current Actual chiller current14 0 to 200 A Chiller Current Limit Chiller current limit15 - °C Current Setpoint Current setpoint value16 - - Control Point Control point17 0 to 1 - Emergency Stop Emergency stop18 0 to 100 % Active Demand Limit Val Active demand limit value* Depends on the selected language (English by default)