216.4 - Configuration menuIcon Displayed text* Description Associated tableGeneral Configuration General configuration GEN_CONFPump Configuration Pump configuration PUMPCONFUser Configuration User configuration USERCONFReset Configuration Reset configuration RESETCFGSchedule Menu Schedule menu SCHEDULEHoliday Menu Holiday menu HOLIDAYBroadcast Menu Broadcast menu BROCASTSDate/Time Configuration Date/time configuration DATETIMEControl Identification Control identification CTRL_ID*Depends on the selected language (English by default)...GEN_CONF.–.General.configurationNo. Status Default Unit Displayed text* Description1 0 to 2 0 - Cir Priority Sequence Circuit priority2 0=Auto, 1=A Prio 0 = Automatic circuit selection1 = Circuit A priority3 2=B Prio 2 = Circuit B priority4 no/yes no - Staged Loading Sequence Staged loading sequence5 no/yes no - Ramp Loading Select Ramp loading selection6 1 to 15 1 min Unit Off to On Delay Unit Off to On delay7 00:00 0 - Night Mode Start Hour Night mode start time8 00:00 0 - Night Mode End Hour Night mode end time9 0 to 100 100 % Night Capacity Limit Night capacity limit10 Basic Menu Configuration Basic menu configuration11 0 = All Access 0 = All access12 1 = no alarm menu 1 = No alarm menu13 2 = no setpoint menu 2 = No setpoint menu14 3 = 1 + 2 3 = No alarm and no setpoint menu15 0 to 2 0 - Demand Limit Type Select Demand limit selection16 0 = None 0 = None17 1 = Switch Control 1 = Switch control18 2 = 4-20mA Control 2 = 4-20 mA control19 0 to 20 0 mA mA For 100% Demand Limit 100% demand Limit (mA)20 0 to 20 10 mA mA For 0% Demand Limit 0% demand Limit (mA)21 no/yes no - Current Limit Select Current limit selection22 0 to 4000 2000 A CurrentLimit at 100% Current limit at 100%23 14.4 to 15 10 ^C Free Cooling Delta T Th Free cooling delta temperature24 20 to 300 30 min Full Load Timeout Full load timeout25 no/yes no - Ice Mode Enable Ice mode enabled26 no/yes no - Reverse Alarms Relay Reverse alarms relay*Depends on the selected language (English by default).