No.4ItemAir speedselection(Continued):Outline of specifications RemarksSelection of highceiling typeCODE No.:[5d] or selection ofhigh ceiling on P.C.board SW501However only whenTcj:Indoor heat exchangersensor temperaturethe high ceilingselection is set to[Standard]CODE No.[5d]SW501 (1)/(2)TapF1F2F3F4F5F6F7F8F9FAFBFCFDStandard Type 1 Type 30 1 3OFF/OFF ON/OFF OFF/ONCOOL COOL COOLHHHHH+H+, HH L+H+ LHLL+LUL UL ULL+(˚C)F4F5F547423) In automatic cooling the revolution frequency of (HH) isset larger than that in the standard cooling operation.4) Self-clean operationWhen performing self-clean operation after stopping thecooling operation, the mode becomes [UL].TcTcj[Self-clean ] isdisplayed.HH0131CP 0181CP 0241CP 0251CP 0301CP 0361CP 0401CP 0481CP 0601CPF1 1000 1100 1140 1140 1140 1140 1140 1140 1140F2 830 880 1080 1080 1080 1080 1080 1080 1120F3 800 850 990 990 990 990 1000 1020 1100F4 790 830 990 990 990 990 1000 1000 1080F5 780 820 990 990 990 990 990 990 1040F6 780 790 910 910 910 910 990 990 1040F7 690 710 790 790 790 790 810 860 1000F8 670 700 790 790 790 790 790 840 900F9 660 690 700 700 700 700 780 830 880FA 590 590 660 660 660 660 710 740 780FB 550 550 600 600 600 600 660 680 760FC 550 550 550 550 550 550 640 670 740FD 350 350 350 350 350 350 350 350 350Tap Revolution speed (rpm)* When the factory is shipped, self-clean operation is set.FILE NO. SVM-19024- 38 -