92APPENDIX III. FAN PERFORMANCE (cont.)48TC**06 1 Phase 5 Ton Horizontal SupplyCFMAVAILABLE EXTERNAL STATIC PRESSURE (in. wg)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPStandard Static Option Medium Static Option1500 800 0.39 904 0.49 999 0.60 1087 0.72 1169 0.851625 849 0.48 947 0.59 1038 0.70 1122 0.83 1201 0.961750 899 0.59 992 0.70 1078 0.82 1159 0.95 1235 1.081875 950 0.70 1038 0.82 1120 0.95 1198 1.08 1271 1.222000 1001 0.84 1085 0.96 1163 1.09 1238 1.23 1309 1.382125 1053 0.99 1133 1.12 1208 1.26 1280 1.40 --- ---2250 1106 1.16 1182 1.29 1254 1.44 --- --- --- ---2375 1159 1.34 1231 1.49 --- --- --- --- --- ---2500 --- --- --- --- --- --- --- --- --- ---CFMAVAILABLE EXTERNAL STATIC PRESSURE (in. wg)1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPMedium Static Option1500 1247 0.98 1320 1.13 1390 1.28 1457 1.44 --- ---1625 1276 1.10 1348 1.24 1416 1.40 --- --- --- ---1750 1308 1.22 1377 1.38 --- --- --- --- --- ---1875 1342 1.37 --- --- --- --- --- --- --- ---2000 --- --- --- --- --- --- --- --- --- ---2125 --- --- --- --- --- --- --- --- --- ---2250 --- --- --- --- --- --- --- --- --- ---2375 --- --- --- --- --- --- --- --- --- ---2500 --- --- --- --- --- --- --- --- --- ---NOTE: For more information, see General Fan Performance Notes on page 87.Boldface indicates field --- supplied drive is required.48TC**06 1 Phase 5 Ton Vertical SupplyCFMAVAILABLE EXTERNAL STATIC PRESSURE (in. wg)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPStandard Static Option Medium Static Option1500 848 0.42 968 0.55 1069 0.68 1158 0.80 1238 0.941625 897 0.51 1013 0.65 1111 0.79 1198 0.93 1277 1.071750 947 0.61 1059 0.76 1155 0.91 1240 1.06 1318 1.211875 997 0.72 1105 0.89 1199 1.05 1283 1.21 1359 1.372000 1048 0.85 1153 1.03 1244 1.20 1326 1.37 --- ---2125 1100 1.00 1201 1.19 1290 1.37 --- --- --- ---2250 1152 1.16 1250 1.36 --- --- --- --- --- ---2375 1205 1.34 --- --- --- --- --- --- --- ---2500 --- --- --- --- --- --- --- --- --- ---CFMAVAILABLE EXTERNAL STATIC PRESSURE (in. wg)1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPMedium Static Option Field---Supplied Drive 11500 1312 1.07 1380 1.20 1445 1.34 1506 1.48 --- ---1625 1350 1.21 1418 1.35 1482 1.50 --- --- --- ---1750 1390 1.36 --- --- --- --- --- --- --- ---1875 --- --- --- --- --- --- --- --- --- ---2000 --- --- --- --- --- --- --- --- --- ---2125 --- --- --- --- --- --- --- --- --- ---2250 --- --- --- --- --- --- --- --- --- ---2375 --- --- --- --- --- --- --- --- --- ---2500 --- --- --- --- --- --- --- --- --- ---NOTE: For more information, see General Fan Performance Notes on page 87.Boldface indicates field --- supplied drive is required.1. Recommend using field --- supplied motor pulley (part number KR11HY171) and belt (part number KR30AE039).48TC