Table 6 — Dry Coil Air Delivery* — Horizontal Discharge (Deduct 10% for 208 v)UNITSIZE50HSMOTORSPEED230 AND 460 V HORIZONTAL DISCHARGEExternal Static Pressure (in. wg)0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0018Low Watts 230 225 220 210 195 170 — — — — —Cfm 760 745 725 695 640 540 — — — — —High Watts — — — — 270 235 200 — — — —Cfm — — — — 850 700 450 — — — —024Low Watts 280 275 265 255 250 245 240 — — — —Cfm 820 810 755 700 660 600 560 — — — —Med Watts 365 360 350 345 340 330 320 310 300 — —Cfm 1025 1010 975 940 900 850 800 720 630 — —High Watts — — 490 480 470 460 445 430 410 390 380Cfm — — 1300 1255 1200 1150 1080 1005 915 790 620030Low Watts — — — — — — — — — — —Cfm — — — — — — — — — — —Med Watts — 365 360 360 350 350 — — — — —Cfm — 1060 1020 980 935 880 — — — — —High Watts — — — — 490 485 475 460 450 430 —Cfm — — — — 1270 1220 1170 1100 1020 920 —036Low Watts 520 495 474 458 495 425 — — — — —Cfm 1375 1335 1290 1244 1200 1146 — — — — —Med Watts 575 560 535 510 480 460 440 425 — — —Cfm 1520 1490 1450 1440 1380 1300 1200 1080 — — —High Watts — — — — 650 614 575 540 510 480 —Cfm — — — — 1560 1500 1380 1280 1170 1060 —042Low Watts 730 700 680 645 615 580 535 490 430 — —Cfm 1620 1590 1550 1510 1460 1390 1310 1210 1050 — —High Watts — — — — — 850 800 750 700 650 610Cfm — — — — — 1780 1670 1550 1400 1230 1050048Low Watts 1080 1040 1020 970 910 840 785 730 680 620 540Cfm 2100 2090 2080 2060 1980 1900 1810 1710 1590 1450 1200High Watts 1230 1190 1125 1060 1010 940 880 820 760 710 660Cfm 2390 2340 2280 2210 2150 2030 1900 1770 1630 1480 1300060Low Watts 1150 1100 1050 1010 950 900 850 800 730 650 —Cfm 2500 2410 2330 2260 2170 2080 1990 1880 1750 1580 —High Watts — — — — — 1170 1110 1050 990 920 880Cfm — — — — — 2470 2340 2200 2040 1870 1700*Air delivery values are based on operating voltage of 230 v or460 v, dry coil, without filter or electric heater. Deduct wet coil, filter,and electric heater pressure drops to obtain external static pressureavailable for ducting.NOTES:1. Do not operate the unit at a cooling airflow that is less than350 cfm for each 12,000 Btuh of rated cooling capacity. Indoor coilfrosting may occur at airflows below this point.2. Dashes indicate portions of table that are beyond the blower mo-tor capacity or are not recommended.23