41PACKAGED TERMINAL COOLING UNITWITH HEAT PUMP OR ELECTRIC HEATINGHVAC Guide SpecificationsSize Range: Cooling: 7,100 to 13,700 BtuhHeating: 6,100 to 11,000 Btuh Heat Pump6,400 to 17,000 Btuh ElectricCarrier Model Numbers: 52SC CoolingOnly Unit52SE Unit withElectric Heat52SQ Heat PumpPart 1 — General1.01 SYSTEM DESCRIPTIONSingle piece, thru-the-wall electrically controlled unitusing hermetic rotary compressor for cooling and heatpump or electric resistance heat, as shown on the con-tract drawings.1.02 QUALITY ASSURANCEUnit shall be rated in accordance with ARI Standard310/380-93 and certified by UL and UL, Canada.1.03 DELIVERY, STORAGE, AND HANDLINGUnit shall be stored and handled per manufacturer’srecommendations.Part 2 — Products2.01 EQUIPMENTA. General:Factory-assembled, single-piece heating and/orcooling unit. Contained within the unit enclosureshall be compressor, coils, fans and fan motor, heat-ing means, controls, all wiring and piping, and afull refrigerant charge (R-22).B. Front Panel (supplied with unit) and Wall Sleeve:Wall sleeve and front panel shall be of plastic mate-rial. Front panel to have louvers in front surface.C. Fans and Motor:1. Evaporator (indoor) fan shall be a single-inletsquirrel cage blower with a corrosion-resistantfinish, discharging air upwards. Fan shall bedynamically balanced.2. Condenser (outdoor) fan shall be a propellertype with corrosion-resistant finish, discharg-ing air out the rear of the unit, and shall bedynamically balanced.3. Motor shall be totally enclosed, permanentlylubricated, and multiple speed.D. Compressor:The compressor shall be fully hermetic with inter-nal and external vibration isolation.E. Coils:The coils shall have aluminum plate fins mechani-cally bonded to seamless copper tubes internallyenhanced (grooved) with all joints brazed.F. Refrigerant Components:All piping, compressor, and expansion devices shallbe included.G. Controls and Safeties:1. Controls shall consist of pushbutton OFF/FAN/ HEAT/COOL adjustable thermostat withupper and lower limits, VENT OPEN/CLOSE,and FAN CYCLE switches. Additional con-trols for heat pumps include outdoor coildefrost thermostat.2. Safeties shall consist of automatic reset over-temperature and overcurrent protection forcompressor, inherent, automatic reset over-temperature protection for fan motor; twoovertemperature protectors for heater.H. Operating Characteristics:Unit shall be capable of starting and running at115 F ambient outdoor temperature per maximumload criteria of ARI Standard 310. Compressor withstandard controls shall be capable of operationdown to 25 F ambient outdoor temperature for heatpump and 55 F ambient outdoor temperature forcooling.I. Electrical Requirements:230/208-Volt: Shall be prewired with one plug touse with appropriate wall receptacle as specified onunit nameplate.265-Volt: Shall be hard-wired or cord-connectedthrough subbase.J. Filter:1. One-piece washable type that filters supply air.2. One-piece washable type filter in vent door fil-ters outdoor air.K. Corrosion Protection (CP):Corrosion Protection (CP), for coastal or corrosiveenvironments, prolongs the life of the product. Min-imum requirements are:1. All outdoor-exposed sheet metal parts shall becoated with a polyester thermostat powder coatpaint.2. Compressor and outdoor fan motor finish shallbe capable of withstanding 500 hours of saltspray testing per ASTM B-117.3. Compressor mounting screws shall be Serma-gard coated.4. Outdoor coil fin stock shall be coated and ableto withstand 1000 hours of salt spray testingper ASTM B-117.5. Outdoor coil tube sheets must be made of 316Lstainless steel.GUIDE SPECIFICATIONS