Fault Code 42INDUCER OUTSIDE VALID SPEED RANGE—This fault indicates that inducer motor is not operating atcalculated RPM or has not started within 10 sec after a call for heat.STEP ACTION YES NO GO TO1. Turn power off, remove blower access panel, and disconnect all thermostat leads from furnace con-trol board. — — 22. Turn power on and depress door switch. Use a piece of tape to hold switch closed. — — 33. Jumper R and W/W1 thermostat terminals on furnace control board. — — 44. Observe operation of furnace for next 8 minutes or until fault occurs. — — 55. Does fault occur again? 9 6 —6. Does a different fault occur? 7 60 —7. Go to page number indicated in Index for fault code flashed. — — INDEX8. Go to page number indicated in Index for CLEANUP AND STARTUP INSTRUCTIONS. — — INDEX9. Does fault occur within 11 sec after a call for heat? 52 35 —10. Do you have 120v between I1 and I2 on furnace control board? 11 14 —11. Do you have 120v between terminals PL7-6 and PL7-12? 13 12 —12. You have an open wire or bad terminal on either the BLACK or WHITE wire between furnace con-trol board and inducer motor MTR1. — — 1413. Are all pins and wire leads intact on connectors between furnace control board and inducer motor? 15 14 —14. Fix problem. — — 815. Turn power off and disconnect jumper wire across R and W/W1 thermostat terminals. Turn poweron and wait a few sec for self test before proceeding to next step. — — 1616. Put setup switch SW-4 for EMER. HEAT in ON position. — — 1717. Jumper R and W/W1 thermostat terminals on furnace control board. — — 1818. Does inducer motor turn on? 30 19 —19. Does inducer wheel rub against inducer housing? 14 20 —20. Turn power off. — — 2121. Does inducer wheel turn freely? 24 22 —22. Replace inducer motor or inducer motor assembly. — — 823. Replace furnace control board. — — 824. Disconnect jumper wire across R and W/W1 thermostat terminals and put setup switch SW-4 forEMER. HEAT in OFF position. — — 2525. Turn power on and wait a few sec for self test before proceeding to next step. — — 2626. Check 12-vdc line. To do this, connect a DC voltmeter across terminals PL1-6 BROWN (+) andPL1-7 GREEN (-). Is voltage across BROWN and GREEN wires 11.5 — 12.5 vdc? 27 23 —27. Turn power off. — — 2828. Do you have continuity between PL7-2 and PL1-6? 22 29 —29. You have an open wire or bad terminal on BROWN wire between connectors PL7 and PL1. — — 1430. Disconnect jumper wire across R and W/W1 thermostat terminals and put setup switch SW-4 forEMER. HEAT in OFF position. — — 3131.Check RPM feedback line. To do this, connect a DC voltmeter across terminals PL1-6 BROWN (+)and PL1-5 ORANGE (-), then put setup switch SW-6 for COMPONENT TEST in ON position. Doesvoltage across BROWN and ORANGE wires change between states as shown below?• State 1—OFF (11.5 — 12.5 vdc)• State 2—LOW (10.2 — 11.2 vdc)• State 3—HIGH (8.4 — 9.4 vdc)23 32 —32. Turn power off. — — 3333. Do you have continuity between PL7-1 and PL1-5? 22 34 —34. You have an open wire or bad terminal on ORANGE wire between connectors PL7 and PL1. — — 1435.Does fault occur a few sec after low-pressure switch LPS makes?NOTE: Check for 24v between the N.O. (Normally Open) contact on low-pressure switch LPSand Com on furnace control board to know when low-pressure switch LPS makes.36 48 —36. Is inducer motor rotating in direction shown on inducer housing? 37 22 —37. Turn power off and disconnect jumper wire across R and W/W1 thermostat terminals. — — 3838. Connect 1 side of a slope manometer with a tee to collector box pressure tap. Connect other sidewith a tee to gas valve air pressure fitting. Refer to pressure check diagram in Appendix C. — — 3939. Turn power on and wait several sec, then jumper R and W/W1 thermostat leads on furnace controlboard. — — 4040.Do you have more than 1.0 in. wc pressure drop (0.80 in. wc on trophy unit) across heat exchang-ers when low-pressure switch LPS makes?NOTE: Check for 24v between the N.O. (Normally Open) contact on low-pressure switch LPSand Com on furnace control board to know when low-pressure switch LPS makes.47 41 —41. Turn power off. — — 4242. Is inducer blower wheel okay? 44 43 —29