17LEGENDJUNCTIONTERMINALCONTROL TERMINALFACTORY POWERWIRING (115VAC)FACTORY CONTROLWIRING (24VAC)FIELD CONTROLWIRING (24VAC)CONDUCTOR ONCONTROLFIELD WIRINGSCREW TERMINALEQUIPMENTGROUNDPLUG RECEPTACLENOTES:332710-101 REV. A1. If any of the original equipment wire is replaced use wire rated for 105°C.2. Use only copper wire between the disconnect switch and the furnace junction box (JB).3. This wire must be connected to furnace sheet metal for control to prove flame.4. Symbols are electrical representation only.5. Solid lines inside PCB are printed circuit board conductors and are not included in legend.6. Replace only with a 3 amp fuse.7. Inductor is used with 3/4 hp and 1 hp ECM Blower motors.8. Factory connected when (LGPS) not used.9. Blower off-delay, gas heating selections are (90, 120, 150, 180) seconds, cooling or heat pump90 seconds or 5 seconds when dehumidify call is active.10. Ignition lockout will occur after four consecutive unsuccessful trials for ignition. Control willauto-reset after three hours.11. Any of the 5 wires shown within the NEUTRAL L2 box can be connected to any terminal within the box.12. Blower motor (BLWM) and Inducer motor (IDM) are locked-rotor overload protected by redundantelectronic control circuits.A/C Air Conditioning (Adjustable Airflow -CFM)ACR Air Conditioning Relay, SPST (N.O.)ACRDJ Air Conditioning Relay Defeat JumperBLWM Blower Motor (ECM)CF Continuous Fan (Adjustable Airflow -CFM)COMMR Communication Relay, SPDTCPU Microprocessor / CircuitryDHUM DHUM Connection (24VAC )EAC-1 Electronic Air Cleaner Connection(115VAC 1.0 Amp Max.)EAC-2 Electronic Air Cleaner Connection (Common)FRS Flame Rollout Switch, Man. Reset, SPST(N.C.)FSE Flame-Proving Sensor ElectrodeFUSE Fuse, 3 Amp, Automotive Blade Type,Factory InstalledGV Gas ValveGVR Gas Valve Relay, DPST (N.O.)HPS High-Heat Pressure Switch, SPST (N.O.)HPSR High-Heat Pressure Switch Relay, SPST (N.C.)HSI Hot Surface Igniter (115VAC)HSIR Hot Surface Igniter Relay, SPST (N.O.)HUM 24VAC Humidifier Connection (0.5 Amp Max.)HUMR Humidifier Relay, SPST (N.O.)IDM Inducer Draft Motor, 2-Speed, Shaded PoleIDR Inducer Motor Relay, SPST (N.O.)IHI/LOR Inducer Motor Speed Change Relay, SPDTILK Blower Door Interlock Switch, SPST (N.O.)IND Inductor (Note #7)LED Light Emitting Diode for Status CodesLGPS Low Gas Pressure Switch, SPST (N.O.)LPS Low-Heat Pressure Switch, SPST (N.O.)LS Limit Switch, Auto-Reset, SPST (N.C.)PCB Printed Circuit BoardPL1 12-Circuit ConnectorPL2 4-Circuit HSI & IDM ConnectorPL3 4-Circuit ECM BLWM ConnectorPL4 4-Circuit Model Plug ConnectorPL7 4-Circuit Communication ConnectorPL9 2-Circuit OAT ConnectorPL10 2-Circuit HSI ConnectorPL11 IDM Connector (12-Circuit)PL12 1-Circuit Inductor Splice ConnectorPL13 16-Circuit ECM Blower Ctrl. ConnectorPL14 5-Circuit ECM Blower Power ConnectorSW1-1 Manual Switch, Status Code Recall, SPST (N.O.)SW1-2 Manual Switch, Low-Heat Only, SPST(N.O.)SW1-3 Manual Switch, Low-Heat Rise Adj. SPST (N.O.)SW1-4 Manual Switch, Comfort/Efficiency Adjustment,SPST (N.O.)SW1-5 Manual Switch, Cooling CFM/Ton, SPST (N.O.)SW1-6 Manual Switch, Component Test, SPST (N.O.)SW1-7,8 Manual Switches, Blower Off-Delay, SPST(N.O.)SW4-1 Manual Switch, Twinning Main (OFF) / Sec. (ON)SW4-2&3 FOR FUTURE USETRAN Transformer, 115VAC / 24VACGVMC HINOTE #3BLUBRNHPSGRN/YELFRSLSNOTE #8GRYRED RED REDLPS(WHEN USED)LGPSBRNFSEWHTPL314HSIL1FUSED OR CIRCUITBREAKER DISCONNECTSWITCH (WHEN REQ'D)NOTE #2GNDNEUTRALFU2BLKILKPL10JB12BLKWHTPL1TRANBLWML1EAC-1PL12INDNOTE #7PL124HSIPL2VSBLKWHTWHTBLUSEC-2CODESEC-1HUMFUSE 3-AMPW/W1DHUM G 24VomCW2 Y/Y2 RY1 STATUSLEDSCOMMACRDJPL8PL9OATSW4PL7A B C DCFACSW1PL4GRN/YEL1. Default A/C airflow when A/C switches are in OFF position2. Default cont. fan airflow when CF switches are in OFF positionA/C OR CF AIRFLOW SELECTION CHART BASED ON 350 CFM/TON1HSI2SCHEMATIC DIAGRAMIDRTO 115VAC FIELD-DISCONNECT SWITCHILKEQUIPMENTGROUND123HSIRIHI/LORPL2L2L2FU1NOTE #6PL1-8RPL1-6L2PL104CPUNOTE #5 PCBPL31 2 3 4BLWMPL131016175 43 21EAC-1PL14PL12INDNOTE #7PL12L1EAC EAC-2TRAN115VACL1 L2SEC2SEC124VACPL1-12HPSRGVLPSNOTE #8LGPS(WHEN USED) HPSHIPL1-2PL1-4PL1-3PL1-10PL1-5W/W1CPUGVRDHUMW2Y/Y2GY1COM NOTE #3CMPL1-1 FSENOTE #5ACRCOMMRPCB1112 2100175014001225122512251225105010508758757007005251205T080,100DEF.DEF.DEF.0603.5T080SIZEMODEL1 2 3OFF1 2 3OFF1 2 3OFF1 2 3OFF1 2 3OFF1 2 3OFF1 2 3OFF1 2 3OFFORNBLKGRN/YEL516 1 710 BLUYELGRNREDPL13 PL14BLKYELCONNECTION DIAGRAMBLKWHTYEL14 3 2BLUYELGRNREDSW1-7,8BLOWER OFF DELAYSELECTION90SEC120SEC150SEC180SECOFF OFF OFF OFF7 8 7 8 7 8 7 811211ACRDJPRINTED CIRCIUT BOARDPRINTED CIRCIUT BOARDHUMRHUMREDMODEL MODELSIZE PLUGHK70EZPIN RESISTANCE K1 - 4 2 - 30603.5T0805T-0801000570580590602424242491120150180PL4 - MODEL PLUG CHART120 061 24 2202700 875 1050 1225 1400 11750 1750IDMGRN/YELBRNORNYELWHTBLKBLKWHTFRS LSIDMPL11PL1-9PL1-11PL1-7L2NOTE #11NEUTRAL - L2EAC-2WHT RED42101126 42101126* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * ** * * * * * * * * * ** * * * ** * * * * * * * * * * * ** * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * * ** * ** ** ** * * * * * ** * * ** ** * * * * * ** * *** * * * * * * ** * * * * * * ** * ** * * * ** * * * * * *** * * * * ** * * * * * * * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * * * * * * * * * * ** * * * *** * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * ** * * * * * * * * * ** * * * ** * * * * * * * * * * * ** * * * * * * * * * * * * * ** * * * * * * * * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * ** ** * ** ** ** * * * * * ** * * ** ** * * * * * ** * *** * * * * * * ** * * * * * * ** * ** * * * ** * * * * *** * * * * ** * * * * * * * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * * * * * * * * * * ** * * * * *A06459Fig. 23 --- Wiring DiagramUNIT DAMAGE HAZARDFailure to follow this caution may result in unit componentdamage.DO NOT connect furnace control HUM terminal to HUM(humidifier) terminal on Thermidistatt, Zone Controller orsimilar device. See Thermidistatt, Zone Controller,thermostat, or controller manufacturer’s instructions forproper connection.CAUTION! 2. Humidifier (HUM)Connect an accessory 24 VAC, 0.5 amp maximumhumidifier (if used) to the 1/4--in. male quick--connectHUM terminal and COM--24V screw terminal on thecontrol board thermostat strip. The HUM terminal isenergized when blower is energized in heating. (See Fig.23 and 33.)Step 8 —Removal of Existing Furnaces fromCommon Vent SystemsWhen an existing Category I furnace is removed or replaced, theoriginal venting system may no longer be sized to properly ventthe remaining attached appliances. An improperly sized CategoryI venting system could cause the formation of condensate in thefurnace and vent, leakage of condensate and combustionproducts, spillage of combustion products into the living space,etc.58UVB