37Table 34 — Dual Slave Chiller Control Parameters for Series Applications with Touch Pilot DisplayNOTE: If pump control is configured to OFF, then LAG UNIT PUMPSELECT = 1. If pump control is set to any other value, then LAGUNIT PUMP SELECT = 0. This configuration must be set consis-tently for both master and slave chillers.Table 35 — Dual Slave Chiller Control Parameters for Series Applications with Navigator DisplayNOTE: If pump control is configured to OFF, then LAG UNIT PUMPSELECT = 1. If pump control is set to any other value, then LAGUNIT PUMP SELECT = 0. This configuration must be set consis-tently for both master and slave chillers.DUAL CHILLER PUMP CONTROL FOR SERIESCHILLER APPLICATIONS — Pump control for series chill-er applications is controlled by the master chiller only. Thecontrol of the slave chiller is directed through commands emit-ted by the master chiller. The slave chiller has no action inmaster/slave operations. The slave chiller only verifies thatCCN communication with the master chiller is present. See theDual Chiller Sequence of Operation section on page 68.Night Time/Low Noise Operation — The Com-fortLink™ controls have the ability to lower the sound level ofthe machine by reducing the number of fans that are running,provided that the conditions are acceptable. Reducing the num-ber of running fans also limits the capacity. Three parametersmust be configured for this operation. A start and end time forthe mode of operation is required and an optional capacity limitset point must also be configured.DISPLAY NAME PATH LINE NO. VALUEMaster/Slave Select Main MenuConfigMST_SLV 3 2 (Slave)Default: 0 (Disable)Master Control Type Main MenuConfigMST_SLV 71 (Local Control)2 (Remote Control)3 (CCN Control)Default: 1 (Local Control)Value: Configure for proper control type.Slave Address Main MenuConfigMST_SLV 11Must be set to the Slave Chiller’s address.The master and slave chiller must havedifferent addresses and be on the sameBus NumberDefault: 2Lead Lag Select Main MenuConfigMST_SLV 120 (Master Always Leads)1 (Lag Once Failed Only)2 (Lead/Lag Runtime Select)Default: 0 (Master Always Leads)Lead/Lag Balance Delta Main MenuConfigMST_SLV 16 Range: 40 to 400 hoursDefault: 168 hoursLag Start Timer Main MenuConfigMST_SLV 17 Range: 2 to 30 minutesDefault: 10 minutesLead Pulldown Time Main MenuConfigMST_SLV 18 Range: 0 to 60 minutesDefault: 0 minutesStart If Error Higher Main MenuConfigMST_SLV 19 Range: 3.0 to 18 F (1.7 to 10.0 C)Default: 4.0 F (2.2 C)Lag Minimum Running Time Main MenuConfigMST_SLV 20 Range: 0 to 150 minutesDefault: 0 minutesLag Unit Pump Control Main MenuConfigMST_SLV 210 (Stop If Unit Stops)1 (Run If Unit Stops)Default: 0 (Stop If Unit Stops)Chiller In Series Main MenuConfigMST_SLV 22 YesDefault: NoITEM ITEM EXPANSION PATH VALUEMSSL Master/Slave Select ConfigurationRSET SlaveDefault: DisableSLVA Slave Address ConfigurationRSETMust be set to the Slave Chiller’s address.The master and slave chiller must havedifferent addresses and be on the sameBus NumberDefault: 2LLBL Master Lead Lag Select ConfigurationRSETRange: Always Lead, Lag if Fail,Runtime SelDefault: Always LeadLLBD Lead/Lag Balance Delta ConfigurationRSET Range: 40 to 400 hoursDefault: 168 hoursLLDY Lag Start Delay ConfigurationRSET Range: 2 to 30 minutesDefault: 10 minutesLL.ER Start If Error Higher ConfigurationRSET Range: 3.0 to 18 F (1.7 to 10.0 C)Default: 4.0 F (2.2 C)LAG.M Lag Unit Pump Select ConfigurationRSET Range: Off If U Stp, On If U StopDefault: Off If U StpLPUL Lead Pulldown Time ConfigurationRSET Range: 0 to 60 minutesDefault: 0 minutesSERI Chillers in Series ConfigurationRSET YESDefault: NOOPER Operating Control Type Operating ModesSLCT CCN Control