5LEGEND*Air Conditioning and Refrigeration Institute (U.S.A.).NOTES:1. Rated in accordance with ARI Standard 550/590-98 at standard rating conditions.2. Standard rating conditions are as follows:Cooler Conditions:Leaving water temperature: 44 F (6.7 C)Entering water temperature: 54 F (12.2 C)Fouling Factor:0.00010 hr x sq ft °F/Btu (0.000018 m2 x °C/W)Condenser Conditions:Entering Air Temperature: 95 F (35 C)3. All data in this table is rated in accordance with ARI Standard 550/590.30XA UNITSIZECAPACITY TOTAL POWER(kW)FULL LOAD IPLV COOLERFLOW RATECOOLERPRESSURE DROP(TONS) (kW) (EER) (COP) (EER) (COP) (gpm) (L/s) (ft wg) (kPa)080 75.4 265.3 83.7 9.9 2.8 14.2 4.0 180.4 11.4 11.4 34.1090 84.4 297.0 84.6 10.7 3.0 14.5 4.1 201.9 12.7 10.6 31.7100 94.3 331.7 97.7 10.5 3.0 14.8 4.2 225.5 14.2 13.2 39.5110 102.4 360.3 108.3 10.4 2.9 15.1 4.3 244.9 15.5 12.5 37.4120 110.7 389.5 119.1 10.3 2.9 15.1 4.3 264.8 16.7 12.6 37.7140 132.9 467.4 135.6 10.7 3.1 14.3 4.1 317.8 20.0 13.9 41.6160 152.6 536.9 160.0 10.6 3.0 14.4 4.1 365.1 23.0 14.6 43.7180 171.3 602.5 176.3 10.7 3.0 14.3 4.1 409.6 25.8 13.1 39.2200 194.0 682.4 201.4 10.7 3.1 14.8 4.2 463.9 29.3 13.9 41.6220 211.6 744.1 222.3 10.6 3.0 14.3 4.1 505.9 31.9 14.1 42.2240 228.2 802.7 247.0 10.4 3.0 14.8 4.2 545.8 34.4 14.5 43.4260 251.0 882.8 261.9 10.7 3.0 14.3 4.1 600.3 37.9 14.4 43.1280 268.6 944.6 280.1 10.7 3.0 14.4 4.1 642.2 40.5 14.3 42.8300 287.5 1011.2 305.2 10.6 3.0 14.6 4.2 687.5 43.4 13.5 40.4325 306.7 1078.6 323.3 10.6 3.0 14.3 4.1 733.4 46.3 13.7 41.0350 324.3 1140.4 351.1 10.4 3.0 14.3 4.1 775.4 48.9 13.8 41.3400 383.7 1349.5 423.0 10.2 2.9 14.7 4.2 917.6 57.9 10.7 32.0450 426.2 1499.1 482.1 10.0 2.8 14.1 4.0 1019.3 64.3 10.7 32.0500 457.0 1607.2 523.5 9.9 2.8 14.2 4.1 1092.8 68.9 11.5 34.4COP — Coefficient of PerformanceEER — Energy Efficiency RatioIPLV — Integrated Part Load ValueARI* capacity ratings (English and SI)