GB - 3AQUASMART Room ControllerE N G L I S H• Match and connect equipment wires to proper terminals in theconnector block.Both power and communication wires must be connectedcorrectly for proper Room Controller operation.• Push any excess wire into the wall and against mountingbase.If the air sensor is being used on the Room Controller, sealhole in wall to prevent air leaks.Leaks can affect sensor operation.• Push the Room Controller snap hinge to the base.MountingWARNING:Before installing the Room Controller, turn off all power tothe Unit that will supply power to the Room Controller.Electrical shock can cause personal injury or death.• Turn OFF all power to unit.• Open the Room Controller rear mounting base to exposemounting holes.The base can be removed to simplify mounting (snap apartcarefully at hinge to separate mounting base from remainderof the Room Controller).• Route the Room Controller wires through the large hole inthe mounting base.Level mounting base against wall (for aesthetic value only theRoom Controller need not be level for proper operation) andmark the wall through the 2 mounting holes.• Drill two 5 mm mounting holes in wall where marked.• Secure mounting base correctly ( ) to wall with 2 screwsand anchors provided, (additional anchoring holes availablefor more secure mounting if needed) making sure all wiresextend through hole in mounting base.• Adjust length and routing of each wire to reach the properterminal in the connector block on the mounting base, with 6mm of extra wire (strip only 6 mm of insulation from each wireto prevent adjacent wires from shorting together whenconnected).Installation Mounting screws To indoor unit Rigid PVCconduit insideø 30mm min.Plaster approx30 mmRoomController ConnectorblockConnection cableConnection cableGPCGPCGPC