Installing the AppControllerAppController CARRIER CORPORATION ©2019Installation and Start-up Guide All rights reserved74 Set the communication type and baud rate.For...Set CommunicationsSelection jumper to... Set DIP switches 1 and 2 to... Set DIP switches 3 and 4 to...MS/TP BACnet MS/TP The appropriate baud rate. See theMS/TP Baud diagram on thecontroller.Off/OffARC156 BACnet ARC156 N/A. Baud rate will be 156 kbpsregardless of the DIP switchsettings.Off/OffNOTE Use the same baud rate for all controllers on the network segment.5 Wire the controllers on a BACnet MS/TP or BACnet ARC156 network segment in a daisy-chain configuration.6 If the AppController is at either end of a network segment, connect a BT485 to the AppController.7 Insert the power screw terminal connector into the AppController's power terminals.8 Verify communication with the network by viewing a Module Status report in the i-Vu® interface.Wiring inputs and outputsWARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.See Appendix A (page 23) to print a blank wire list.Input wiring specificationsInput Maximum length Minimum gauge Shielding0–5 Vdc 500 feet(152 meters)22 AWG 100 feet(30.4 meters) unshielded100 - 500 feet shieldedThermistorDry contactPulse counter TLO500 feet(152 meters)22 AWG 100 feet(30.4 meters) unshielded100 - 500 feet shieldedZS sensorsWireless Adapter forwireless sensorsEquipment TouchTruVu™ ET DisplaySee Wiring devices to the AppController's Rnet port (page 11).