436 - ELECTRICAL CONNECTION6.4.2 - On-site control wiringSelection of minimum and maximum wire sections for connection to 61WG units61WGMax.connectablesection (1)Calculation favourable case: Suspended aerial lines(standardised routing No. 17)PVC insulated cableCalculation unfavourable case: Conductors inconduits or multi-conductor cables in closed conduit(standardised routing No. 41)PVC insulated cable, if possibleSection Section(2) Max. length for voltage drop<5% CabletypeSection(2) Max. length for voltage drop<5% Cabletypeemm²(per phase)mm²(per phase) m mm²(per phase) m20 1 x 35 1 x 2.5 60 PVC Cu 1 x 2.5 60 PVC Cu25 1 x 35 1 x 2.5 60 PVC Cu 1 x 2.5 60 PVC Cu30 1 x 35 1 x 4 80 PVC Cu 1 x 4 80 PVC Cu35 1 x 35 1 x 4 80 PVC Cu 1 x 4 80 PVC Cu40 1 x 35 1 x 6 100 PVC Cu 1 x 6 100 PVC Cu45 1 x 35 1 x 6 100 PVC Cu 1 x 6 100 PVC Cu50 1 x 35 1 x 10 120 PVC Cu 1 x 10 120 PVC Cu60 1 x 35 1 x 10 120 PVC Cu 1 x 10 120 PVC Cu70 1 x 35 1 x 16 140 PVC Cu 1 x 16 140 PVC Cu80 1 x 35 1 x 16 140 PVC Cu 1 x 16 140 PVC Cu90 1 x 35 1 x 25 170 PVC Cu 1 x 25 170 PVC CuSelection of minimum and maximum wire sections for connection to 30WG/30WGA units30WG30WGAMax.connectablesection (1)Calculation favourable case: Suspended aerial lines(standardised routing No. 17)PVC insulated cableCalculation unfavourable case: Conductors inconduits or multi-conductor cables in closed conduit(standardised routing No. 41)PVC insulated cable, if possibleSection Section(2) Max. length for voltage drop<5% CabletypeSection(2) Max. length for voltage drop<5% Cabletypeemm²(per phase)mm²(per phase) m mm²(per phase) m20 1 x 35 1 x 2.5 60 PVC Cu 1 x 2.5 60 PVC Cu25 1 x 35 1 x 2.5 60 PVC Cu 1 x 2.5 60 PVC Cu30 1 x 35 1 x 4 80 PVC Cu 1 x 4 80 PVC Cu35 1 x 35 1 x 4 80 PVC Cu 1 x 4 80 PVC Cu40 1 x 35 1 x 6 100 PVC Cu 1 x 6 100 PVC Cu45 1 x 35 1 x 6 100 PVC Cu 1 x 6 100 PVC Cu50 1 x 35 1 x 10 120 PVC Cu 1 x 10 120 PVC Cu60 1 x 35 1 x 10 120 PVC Cu 1 x 10 120 PVC Cu70 1 x 35 1 x 16 140 PVC Cu 1 x 16 140 PVC Cu80 1 x 35 1 x 16 140 PVC Cu 1 x 16 140 PVC Cu90 1 x 35 1 x 25 170 PVC Cu 1 x 25 170 PVC Cu61WG/30WG/30WGAMax.connectablesection (1)Calculation favourable case: Suspended aerial lines(standardised routing No. 17)PVC insulated cableCalculation unfavourable case: Conductors inconduits or multi-conductor cables in closed conduit(standardised routing No. 41)PVC insulated cable, if possibleSection Section(2) Max. length for voltage drop<5% CabletypeSection(2) Max. length for voltage drop<5% Cabletypeemm²(per phase)mm²(per phase) m mm²(per phase) m110 1 x 95 1 x 25 163 XLPE Cu 1 x 50 317 XLPE Cu120 1 x 95 1 x 25 149 XLPE Cu 1 x 50 291 XLPE Cu140 1 x 95 1 x 25 134 XLPE Cu 1 x 70 360 XLPE Cu150 1 x 95 1 x 35 175 XLPE Cu 1 x 70 338 XLPE Cu170 1 x 95 1 x 35 157 XLPE Cu 1 x 95 403 XLPE Cu190 1 x 95 1 x 50 197 XLPE Cu 1 x 95 358 XLPE Cu(1) Connection capacities actually available for each machine, defined according to the connection terminal size, the control box access opening size and the availablespace inside the control box.(2) Selection simultation result considering the hypothesis indicated.(3) If the maximum calculated section is for an XLPE cable type, this means that a selection based on a PVC cable type can exceed the connection capacity actuallyavailable. Special attention must be given to the selection.Note: The currents considered are given for a machine equipped with a hydraulic module operating at maximum current.6.5 - 24 V user power reserveAfter all possible options have been connected, the trans-former ensures the availability of a usable 24 VA or 1 A power reserve for thecontrol circuit on site.