12Dimensions38AP UNITS, SIZES 025-030a38-7101P4.62117.4[ ]1.50 38.1[ ] 1.50 38.1[ ]SEE NOTE #4TYP.1.00 25.4[ ]SEE NOTE #4TYP.1.00 25.4[ ]11.81 300.0[ ]8.52216.4[ ]9.52241.8[ ]40.34 1024.5[ ]YXHSEE NOTE #615.31 388.9[ ]36 [914] MIN.42 [1067]MIN.36 [914] MIN.48 [1219]MIN.FIELD POWER ENTRYSEE NOTE #37/8 22.4[ ]RADIUS 20 [508]CONTROL BOXHINGED ACCESS21.06 534.9[ ]24.56 623.8[ ]88.24 2241.3[ ] TOP VIEWCGSERVICECLEARANCEBORDER(NOT TO SCALE)COIL SIDESEE NOTE #5PANEL SIDESEE NOTE #5AIR FLOWCOIL AREARIGHT SIDEVIEWCOIL SIDESEE NOTE #5SEE NOTE'S #1,2FRONT VIEWAIR FLOWFIELD CONTROLWIRING CONNECTIONSLOW SOUND FAN STACK(PICTORIALLY ONLY)CONTROL BOXHINGED ACCESSCIRCUIT ALIQUID CONNECTIONCIRCUIT ASUCTION CONNECTIONCIRCUIT BSUCTION CONNECTIONCIRCUIT BLIQUID CONNECTION SERVICEACCESSCOMPRESSORACCESSUNIT STANDARDWEIGHT, lb (kg)CENTER OF GRAVITY,in. (mm)HEIGHT,in. (mm)POWER ENTRY,in. (mm)SERVICE VALVECONNECTIONS, in. (mm)X Y H P Suction LiquidStandard38APS025 1077 (489) 17.8 (452) 36.9 (937) 61.0 (1549) 24.9 (632) 1 5 /8 (41) 5 /8 (16)38APD025 1095 (497) 17.8 (452) 37.0 (940) 1 3 /8 (35) 5 /8 (16)38APS027 1240 (563) 18.2 (462) 37.6 (955)73.1 (1857) 36.9 (937)1 5 /8 (41) 5 /8 (16)38APD027 1258 (571) 18.2 (462) 37.6 (955) 1 3 /8 (35) 5 /8 (16)38APS030 1246 (565) 18.2 (462) 37.5 (953) 1 5 /8 (41) 7 /8 (22)38APD030 1264 (573) 18.2 (462) 37.6 (955) 1 3 /8 (35) 5 /8 (16)Low Sound38APS025 1113 (505) 17.8 (452) 36.9 (937) 66.5 (1689) 24.9 (632) 1 5 /8 (41) 5 /8 (16)38APD025 1131 (513) 17.8 (452) 37.0 (940) 1 3 /8 (35) 5 /8 (16)38APS027 1276 (579) 18.2 (462) 37.6 (955)78.6 (1996) 36.9 (937)1 5 /8 (41) 5 /8 (16)38APD027 1294 (587) 18.2 (462) 37.6 (955) 1 3 /8 (35) 5 /8 (16)38APS030 1282 (582) 18.2 (462) 37.5 (953) 1 5 /8 (41) 7 /8 (22)38APD030 1300 (590) 18.2 (462) 37.6 (955) 1 3 /8 (35) 5 /8 (16)NOTES:1. Be sure to use a wet rag to remove all valve cores before brazing field piping.2. Do not cap or otherwise obstruct the liquid line temperature relief.3. A 7/ 8 in. (22.4 mm) diameter hole is provided for locating field power wiring. Actual hole sizerequired depends on field wire sizing.4. A 0.437 in. (11.1 mm) diameter hole is used for mounting unit.5. Unit must have clearances as follows:Top - Do not restrict.Coil End - 42 in. (1067) from solid surface.Panel Side - 48 in. (1219) per NEC (National Electrical Code).6. Unit height (dimension H) for the low sound fan option includes the fan stack.7. Installation in a pit is not recommended.8. Unit can be handled using the fork truck lift pockets.9. Dimensions shown in inches (mm).10. Weight does not include unit refrigerantcharge.