8coil sections. Dirt and debris may pass through first section,become trapped between the row of fins and restrict condenserairflow. Use a flashlight to determine if dirt or debris has collectedbetween coil sections. Clean coil as follows:1. Turn off unit power.2. Using a garden hose or other suitable equipment, flush coilfrom the outside to remove dirt. Be sure to flush all dirt anddebris from drain holes in base of unit. Fan motors are wa-terproof.Table 1—Superheat ChargingOUT---DOORTEMP° F(° C)EVAPORATOR ENTERING AIR TEMPERATURE ° F (° C) WB50(10)52(11)54(12)56(13)58(14)60(16)62(17)64(18)66(19)68(20)70(21)72(22)74(23)76(24)55(13)9( ---13)12( ---11)14( ---10)17( ---8)20( ---7)23( ---5)26( ---3)29( ---2)32(0)35(2)37(3)40(4)42(6)45(7)60(16)7( ---14)10( ---12)12( ---11)15( ---9)18( ---8)21( ---6)24( ---4)27( ---3)30( ---1)33(1)35(2)38(3)40(4)43(6)65(18) — 6( ---14)10( ---12)13( ---11)16( ---9)19( ---7)21( ---6)24( ---4)27( ---3)30( ---1)33(1)36(2)38(3)41(5)70(21) — — 7( ---14)10( ---12)13( ---11)16( ---9)19( ---7)21( ---6)24( ---4)27( ---3)30( ---1)33(1)36(2)39(4)75(24) — — — 6( ---14)9( ---13)12( ---11)15( ---9)18( ---8)21( ---6)24( ---4)28( ---2)31( ---1)34(1)37(3)80(27) — — — — 5( ---15)8( ---13)12( ---11)15( ---9)18( ---8)21( ---6)25( ---4)28( ---2)31( ---1)35(2)85(29) — — — — — — 8( ---13)11( ---12)15( ---9)19( ---7)22( ---6)26( ---3)30( ---1)33(1)90(32) — — — — — — 5( ---15)9( ---13)13( ---11)16( ---9)20( ---7)24( ---4)27( ---3)31( ---1)95(36) — — — — — — — 6( ---14)10( ---12)14( ---10)18( ---8)22( ---6)25( ---4)29( ---2)100(38) — — — — — — — — 8( ---13)12( ---11)15( ---9)20( ---7)23( ---5)27( ---3)105(41) — — — — — — — — 5( ---15)9( ---13)13( ---11)17( ---8)22( ---6)26( ---3)110(43) — — — — — — — — — 6( ---14)11( ---12)15( ---9)20( ---7)25( ---4)115(47) — — — — — — — — — — 8( ---13)14( ---10)18( ---8)23( ---5)Where a dash ( ---) appears, do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weight in.NOTE: Superheat _F (_C) is at low---side service port.Table 2—Required Suction--Line TemperatureSUPERHEATTEMP(°F/°C)SUCTION PRESSURE AT SERVICE PORT (PSIG)107.8 112.2 116.8 121.2 126.0 130.8 138.8 140.8 145.80/--- 18 35 37 39 41 43 45 47 49 512/--- 17 37 39 41 43 45 47 49 51 534/--- 16 39 41 43 45 47 49 51 53 556/--- 14 41 43 45 47 49 51 53 55 578/--- 13 43 45 47 49 51 53 55 57 5910/--- 12 45 47 49 51 53 55 57 59 6112/--- 11 47 49 51 53 55 57 59 61 6314/--- 10 49 51 53 55 57 59 61 63 6516/--- 9 51 53 55 57 59 61 63 65 6718/--- 8 53 55 57 59 61 63 65 67 6920/--- 7 55 57 59 61 63 65 67 69 7122/--- 6 57 59 61 63 65 67 69 71 7324/--- 4 59 61 63 65 67 69 71 73 7526/--- 3 61 63 65 67 69 71 73 75 7728/--- 2 63 65 67 69 71 73 75 77 7930/--- 1 65 67 69 71 73 75 77 79 8132/0 67 69 71 73 75 77 79 81 8334/1 69 71 73 75 77 79 81 83 8536/2 71 73 75 77 79 81 83 85 8738/3 73 75 77 79 81 83 85 87 8940/4 75 77 79 81 83 85 87 89 9138QRR