Appendix A: VVT Zone II Points/PropertiesVVT Zone II Controller CARRIER CORPORATION ©2019Installation and Start-up Guide All rights reserved87LinkageNavigation: i-Vu® / Field Assistant: Properties > Equipment > LinkagePoint Name/Description Default/RangeAirside LinkageClick Linkage Collector/Linkage Provider to access the microblock popup's Summaryand Details tabs. See the microblock popup's Help for more detailed explanations.Linkage Collector – Set the Number of Providers to the total number of controllers inthe linked system, including the bypass and VVT Master.D:R:11 to 32Linkage Provider – Enter the MS/TP Network Number and MAC Address of the linkedair source controller.Network NumberAddressNOTE If you change the Network Number or Address, you must use the i-Vu®application or Field Assistant to cycle power to the controller for the changes to takeeffect.D:R:D:R:00 to 6553500 to 99Airside Linkage Status – If Active, the controller is part of a linked system. If Not Active,the controller is a stand-alone device.R: Not Active/ActiveLinkage Zone Type – Select whether the controller is a Master or a slave.Select VAV Master if the controller is the Master or a sub-master in a VAV application.Select VVT Master only if the controller is the Master in a VVT application. VVTapplications do not support sub-masters.D:R:SlaveSlaveVVT MasterVAV MasterInhibit Heating Call from this zone? - If Yes, the VVT Master ignores this controller as aheating caller.D:R:NoNo/YesActive Heating Caller? – Displays if this zone is currently an active heat caller for thesystem.D:R:YesNo/YesInhibit Cooling Call from this zone? - If Yes, the VVT Master ignores this controller as acooling caller.D:R:NoNo/YesActive Cooling Caller? – Displays if this zone is currently an active cooling caller for thesystem.D:R:YesNo/YesLinkage Callers – The minimum number of zones required to make the air source gointo heating or cooling mode. 1 is typical for systems with 8 zones or less. For largersystems, increase the number by 1 for each 6 zones. For example, 3 linkage callers fora 20 zone system.D:R:11 to 32