133APPENDIX A — LOCAL DISPLAY TABLESMODE — RUN STATUSITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS PAGE NO.VIEW AUTO VIEW OF RUN STATUS→HVAC ascii string spelling out the hvac modes string 90,92→OCC Occupied ? YES/NO OCCUPIED forcible 90,92→MAT Mixed Air Temperature dF MAT 90,92→EDT Evaporator Discharge Tmp dF EDT 90,92→LAT Leaving Air Temperature dF LAT 90,92→EC.C.P Economizer Control Point dF ECONCPNT 90,92→ECN.P Economizer Act.Curr.Pos. 0-100 % ECONOPOS 90,92→EC2.P Economzr Act.Curr.Pos. 0-100 % ECON2POS 90,92→CL.C.P Cooling Control Point dF COOLCPNT 90,92→C.CAP Current Running Capacity CAPTOTAL 90,92→CL.ST Requested Cool Stage CL_STAGE 90,92→HT.C.P Heating Control Point dF HEATCPNT 90,92→HT.ST Requested Heat Stage HT_STAGE 90,92→H.MAX Maximum Heat Stages HTMAXSTG 90,92ECON ECONOMIZER RUN STATUS→ECN.P Economizer Act.Curr.Pos. 0-100 % ECONOPOS 69,93→EC2.P Economzr 2 Act.Curr.Pos. 0-100 % ECON2POS 69,93→ECN.C Economizer Act.Cmd.Pos. 0-100 % ECONOCMD forcible 69,93→ACTV Economizer Active ? YES/NO ECACTIVE 69,93→DISA ECON DISABLING CONDITIONS→DISA→UNV.1 Econ Act. Unavailable? YES/NO ECONUNAV 69,93→DISA→UNV.2 Econ2 Act. Unavailable? YES/NO ECN2UNAV 69,93→DISA→ENTH Enth. Switch Read High ? YES/NO ENTH 69,93→DISA→DBC DBC - OAT Lockout? YES/NO DBC_STAT 69,93→DISA→DEW DEW - OA Dewpt.Lockout? YES/NO DEW_STAT 69,93→DISA→DDBC DDBD- OAT > RAT Lockout? YES/NO DDBCSTAT 69,93→DISA→OAEC OAEC- OA Enth Lockout? YES/NO OAECSTAT 69,93→DISA→DEC DEC - Diff.Enth.Lockout? YES/NO DEC_STAT 69,93→DISA→EDT EDT Sensor Bad? YES/NO EDT_STAT 69,93→DISA→OAT OAT Sensor Bad ? YES/NO OAT_STAT 69,93→DISA→FORC Economizer Forced ? YES/NO ECONFORC 69,93→DISA→SFON Supply Fan Not On 30s ? YES/NO SFONSTAT 69,93→DISA→CLOF Cool Mode Not In Effect? YES/NO COOL_OFF 69,93→DISA→OAQL OAQ Lockout in Effect ? YES/NO OAQLOCKD 69,93→DISA→HELD Econ Recovery Hold Off? YES/NO ECONHELD 69,93→DISA→DH.DS Dehumid. Disabled Econ.? YES/NO DHDISABL 69,93→O.AIR OUTSIDE AIR INFORMATION 69,93→O.AIR→OAT Outside Air Temperature dF OAT forcible 69,93→O.AIR→OA.RH Outside Air Rel. Humidity % OARH forcible 69,93→O.AIR→OA.E Outside Air Enthalpy OAE 69,93→O.AIR→OA.D.T OutsideAir Dewpoint Temp dF OADEWTMP 69,93COOL COOLING INFORMATION→C.CAP Current Running Capacity % CAPTOTAL 92,93→CUR.S Current Cool Stage COOL_STG 92,93→REQ.S Requested Cool Stage CL_STAGE 92,93→MAX.S Maximum Cool Stages CLMAXSTG 92,93→DEM.L Active Demand Limit % DEM_LIM forcible 92,93→SUMZ COOL CAP. STAGE CONTROL→SUMZ→SMZ Capacity Load Factor -100 → +100 SMZ 92,93→SUMZ→ADD.R Next Stage EDT Decrease ^F ADDRISE 92,93→SUMZ→SUB.R Next Stage EDT Increase ^F SUBRISE 92,93→SUMZ→R.PCT Rise Per Percent Capacity RISE_PCT 92,93→SUMZ→Y.MIN Cap Deadband Subtracting Y_MINUS 92,93→SUMZ→Y.PLU Cap Deadband Adding Y_PLUS 92,93→SUMZ→Z.MIN Cap Threshold Subtracting Z_MINUS 92,93→SUMZ→Z.PLU Cap Threshold Adding Z_PLUS 92,93→SUMZ→H.TMP High Temp Cap Override HI_TEMP 92,93→SUMZ→L.TMP Low Temp Cap Override LOW_TEMP 92,93→SUMZ→PULL Pull Down Cap Override PULLDOWN 92,93→SUMZ→SLOW Slow Change Cap Override SLO_CHNG 92,93TRIP MODE TRIP HELPER→UN.C.S Unoccup. Cool Mode Start UCCLSTRT 93→UN.C.E Unoccup. Cool Mode End UCCL_END 93→OC.C.S Occupied Cool Mode Start OCCLSTRT 93→OC.C.E Occupied Cool Mode End OCCL_END 93→TEMP Ctl.Temp RAT,SPT or Zone CTRLTEMP 93→OC.H.E Occupied Heat Mode End OCHT_END 93→OC.H.S Occupied Heat Mode Start OCHTSTRT 93→UN.H.E Unoccup. Heat Mode End UCHT_END 93→UN.H.S Unoccup. Heat Mode Start UCHTSTRT 93→HVAC ascii string spelling out the hvac modes string 93LINK CCN - LINKAGE→MODE Linkage Active - CCN ON/OFF MODELINK 94→L.Z.T Linkage Zone Control Tmp dF LZT 94→L.C.SP Linkage Curr. Cool Setpt dF LCSP 94→L.H.SP Linkage Curr. Heat Setpt dF LHSP 94HRS COMPRESSOR RUN HOURS→HR.A1 Compressor A1 Run Hours 0-999999 HRS HOURS_A1 config 94→HR.A2 Compressor A2 Run Hours 0-999999 HRS HOURS_A2 config 94→HR.B1 Compressor B1 Run Hours 0-999999 HRS HOURS_B1 config 94→HR.B2 Compressor B2 Run Hours 0-999999 HRS HOURS_B2 config 94STRT COMPRESSOR STARTS→ST.A1 Compressor A1 Starts 0-999999 CY_A1 config 94→ST.A2 Compressor A2 Starts 0-999999 CY_A2 config 94→ST.B1 Compressor B1 Starts 0-999999 CY_B1 config 94→ST.B2 Compressor B2 Starts 0-999999 CY_B2 config 94VERS SOFTWARE VERSION NUMBERS→MBB CESR131292-xx-xx string 94→RCB CESR131249-xx-xx string 94→ECB CESR131249-xx-xx string 94→SCB CESR131226-xx-xx string 94→CEM CESR131174-xx-xx string 94→ECON xx-xx-xxx-xxx-xx string 94→IGV xx-xx-xxx-xxx-xx string 94→HUMD xx-xx-xxx-xxx-xx string 94→HEAT xx-xx-xxx-xxx-xx string 94→BP1 xx-xx-xxx-xxx-xx string 94→BP2 xx-xx-xxx-xxx-xx string 94→MARQ CESR131171-xx-xx string 94→NAVI CESR130227-xx-xx string 94