35Configuration→BP→BF.CF=2 (Modulating PowerExhaust with Two LEN Actuators Option) — For modulat-ing exhaust, the Configuration→BP submenu, configure thefollowing:Under Configuration→BP→B.V.A the following configu-rations may be adjusted:BP.FS VFD/Act. Fire Speed/Pos.BP.MN VFD/Act. Min. Speed/Pos.BP.1M BP 1 Actuator Max Pos.BP.2M BP 2 Actuator Max Pos.Configuration→BP→BP.CF=3 (VFD Power ExhaustOption) — Under Configuration→BP the following configu-rations may be adjusted:Under Configuration→BP→B.V.A the following configu-rations may be adjusted:BP.FS VFD/Act. Fire Speed/Pos.BP.MN VFD/Act. Min. Speed/Pos.BP.MX VFD Maximum SpeedConfiguration→BP→BP.CF=4 (High-Capacity VFDPower Exhaust) — Under Configuration→BP the followingconfigurations may be adjusted:Under Configuration→BP→B.V.A the following configu-rations may be adjusted:BP.FS VFD/Act. Fire Speed/Pos.BP.MN VFD/Act. Min. Speed/Pos.BP.MX VFD Maximum SpeedBP.CL BP Hi Cap VFD Clamp Val.BP.WT BP Hi Cap VFD Clamp TimeConfiguration→BP→BP.CF=5 (Return/Exhaust — FanTracking Control) — Under Configuration→ BP the follow-ing configurations may be adjusted:BP.SP Building Pressure Setpt. (see note below)Under Configuration→BP→B.V.A the following configu-rations may be adjusted:BP.FS VFD/Act. Fire Speed/Pos.BP.MN VFD/Act. Min. Speed/Pos.BP.MX VFD Maximum SpeedUnder Configuration→BP→FAN.T the following config-urations may be adjusted:FT.CF Fan Track Learn Enable (see note below)FT.TM Fan Track Learn Rate (see note below, notused when Fan Track Learning is disabled)FT.ST Fan Track Initial DCFMFT.MX Fan Track Max Clamp (see note below, notused when Fan Track Learning is disabled)FT.AD Fan Track Max Correction (see note below,not used when Fan Track Learning is disabled)FT.OF Fan Track Internl EEPROM (see note below,not used when Fan Track Learning is disabled)FT.RM Fan Track Internal Ram (see note below, notused when Fan Track Learning is disabled)FT.RS Fan Track Reset Internal (see note below, notused when Fan Track Learning is disabled)SCF.C Supply Air CFM Config (see note below, notused when Fan Track Learning is disabled)NOTE: These configurations are used only if Fan Trackinglearning is enabled. When fan tracking learning is enabled,the control will add an offset to the Fan Track Initial DCFM(Configuration→BP→FAN.T→FT.ST) if the building pres-sure deviates from the Building Pressure Set Point (BP.SP).Periodically, at the rate set by the Fan Track Learn Rate(FT.TM) the delta cfm is adjusted upward or downward with amaximum adjustment at a given instance to be no greater thanFan Track Max correction (FT.AD). The delta cfm can notever be adjusted greater than or less than the Fan Track MaxClamp (FT.MX).Set Clock on VFD (If Installed) — The clock setmode is used for setting the date and time for the internal clockof the VFD. In order to use the timer functions of the VFDcontrol, the internal clock must be set. The date is used to deter-mine weekdays and is visible in the fault logs. Refer to theVFD section in Appendix D on page 160 for information onoperating the VFD and using the keypad.To set the clock, perform the following procedure from theVFD keypad:1. Select MENU (SOFT KEY 2). The Main menu will bedisplayed.2. Use the UP or DOWN keys to highlight CLOCK SET onthe display screen and press ENTER (SOFT KEY 2). Theclock set parameter list will be displayed.3. Use the UP or DOWN keys to highlight CLOCK VISI-BILITY and press SEL (SOFT KEY 2). This parameteris used to display or hide the clock on the screen. Use theUP or DOWN keys to change the parameter setting. PressOK (SOFT KEY 2) to save the configuration and returnto the Clock Set menu.4. Use the UP or DOWN keys to highlight SET TIME andpress SEL (SOFT KEY 2). Use the UP or DOWN keys tochange the hours and minutes. Press OK (SOFT KEY 2)to save the configuration and return to the Clock Setmenu.5. Use the UP or DOWN keys to highlight TIME FORMATand press SEL (SOFT KEY 2). Use the UP or DOWNkeys to change the parameter setting. Press OK (SOFTKEY 2) to save the configuration and return to the ClockSet menu.6. Use the UP or DOWN keys to highlight SET DATE andpress SEL (SOFT KEY 2). Use the UP or DOWN keys tochange the day, month, and year. Press OK (SOFT KEY2) to save the configuration and return to the Clock Setmenu.7. Use the UP or DOWN keys to highlight DATE FOR-MAT and press SEL (SOFT KEY 2). Use the UP orDOWN keys to change the parameter setting. Press OK(SOFT KEY 2) to save the configuration and return to theClock Set menu.8. Press EXIT (SOFT KEY 1) twice to return to the mainmenu.BP.SP Building Pressure Set pointBP.SO BP Set point OffsetBP.SP Building Pressure Set pointBP.SO BP Set point OffsetBP.SP Building Pressure Set pointBP.SO BP Set point Offset