16your area.) If a de-energize via unit disconnect switch operationof the convenience outlet is desired, connect the source leads tothe load side of the unit disconnect. On a unit without a unit-mounted disconnect, connect the source leads to compressorcontactor C and indoor fan contactor IFC pressure lugs with unitfield power leads. See Convenience Outlets on page 18 for pow-er transformer connections.The field power wires are connected to the unit at line-sidepressure lugs on compressor contactor C and indoor fan con-tactor IFC (see wiring diagram label for control box compo-nent arrangement) or at factory-installed option non-fused dis-connect switch or HACR. Maximum wire size is #2ga AWG(copper only) per pole on contactors and #2ga AWG (copperonly) per pole on optional disconnect or HACR. See Fig. 26and unit label diagram for field power wiring connections.NOTE: Unit may be equipped with short test leads (pigtails) onthe field line connection points on contactor C or optional discon-nect switch. These leads are for factory-run test purposes only; re-move and discard before connecting field power wires to unit con-nection points. Make field power connections directly to line con-nection pressure lugs only.Fig. 26 — Power Wiring ConnectionsFig. 27 — Disconnect Switch and UnitUNITS WITH FACTORY-INSTALLED NON-FUSED DIS-CONNECT OR HACRThe factory-installed option non-fused disconnect (NFD) orHACR switch is located in a weatherproof enclosure locatedunder the main control box. The manual switch handle andshaft are shipped in the disconnect or HACR enclosure. As-semble the shaft and handle to the switch at this point. Discardthe factory test leads (see Fig. 26).Connect field power supply conductors to LINE side terminalswhen the switch enclosure cover is removed to attach the handle.Field-Install the NFD Shaft and Handle1. Remove unit front panel (see Fig. 2).2. Remove (3) hex screws on the NFD enclosure — (2) onthe face of the cover and (1) on the left side cover. SeeFig. 28.3. Remove the front cover of the NFD enclosure.4. Make sure the NFD shipped from the factory is at OFFposition (the arrow on the black handle knob is at OFF).5. Insert the shaft with the cross pin on the top of the shaft inthe horizontal position. See Fig. 29.6. Measure from the tip of the shaft to the top surface of theblack pointer; the measurement should be 3.75 to 3.88 in.(95 to 99 mm).7. Tighten the locking screw to secure the shaft to the NFD.8. Turn the handle to the OFF position with red arrow point-ing at OFF.9. Install the handle on to the painted cover horizontally withthe red arrow pointing to the left.10. Secure the handle to the painted cover with (2) screws andlock washers supplied.11. Engaging the shaft into the handle socket, re-install (3)hex screws on the NFD enclosure.12. Re-install the unit front panel.Fig. 28 — NFD Enclosure LocationWARNINGFIRE HAZARDFailure to follow this warning could result in intermittent oper-ation or performance satisfaction.Do not connect aluminum wire between disconnect switch andunit. Use only copper wire.C11 23DisconnectperNEC208/230-1-60orDisconnectperNEC11 13 13 23L1 L2 L3TBC IFCDirect Drive IFM208/230-3-60460-3-60575-3-60Units Without Disconnect or HACR OptionUnits With Disconnect or HACR OptionL1L2L324615OptionalDisconnectSwitchDisconnect factory test leads; discard.FactoryWiring1-ph Belt Drive IFM3EquipGR LugGround(GR)Ground(GR)EquipGR LugEquip GR LugGround(GR)3 Phase Only 3 Phase OnlyCOPPERWIRE ONLYELECTRICDISCONNECTSWITCHALUMINUMWIRE