52STANDARD MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLETLEGEND*Used to determine minimum disconnect per NEC.†Fuse or HACR circuit breaker per NEC.**Units have 2 condenser-fan motors.NOTES:1. In compliance with NEC requirements for multimotor and combina-tion load equipment (refer to NEC Articles 430 and 440), the over-current protective device for the unit shall be fuse or HACRbreaker. The UL, Canada units may be fuse or circuit breaker.2. Electrical data based on 95 F ambient outdoor-air temperature± 10% voltage.UNIT NOMINALVOLTAGE(V-Ph-Hz)VOLTAGERANGE COMPRESSOR OFM IFM COMBUSTIONFAN MOTORPOWERSUPPLYWITH OUTLETMINIMUM UNITDISCONNECTSIZE*Min Max RLA LRA FLA FLA FLA MCA MOCP FLA LRA48HJE/HJF004(3 Tons)208/230-1-60 187 254 16.0 88.0 0.7 4.9 .57 31.6/31.6 40/40† 30/30 106/106208/230-3-60 187 254 10.3 77.0 0.7 4.9 .57 24.5/24.5 30/30† 24/24 95/95460-3-60 414 508 5.1 39.0 0.4 2.2 .30 11.7 15† 11 48575-3-60 518 632 4.2 31.0 0.4 2.2 .30 9.5 15† 9 3848HJD/HJE/HJF005(4 Tons)208/230-1-60 187 254 23.7 129.0 0.7 4.9 .57 41.2/41.2 50/50† 39/39 147/147208/230-3-60 187 254 13.5 99.0 0.7 4.9 .57 28.5/28.5 35/35† 27/27 117/117460-3-60 414 508 7.4 49.5 0.4 2.2 .30 14.6 20† 14 58575-3-60 518 632 5.8 40.0 0.4 2.2 .30 11.5 15† 11 4748HJD/HJE/HJF006(5 Tons)208/230-1-60 187 254 28.8 169.0 1.5 8.8 .57 52.3/52.3 60/60† 50/50 221/221208/230-3-60 187 254 17.3 123.0 1.5 5.8 .57 34.9/34.9 40/40† 34/34 173/173460-3-60 414 508 9.0 62.0 0.8 2.6 .30 17.4 20† 17 86575-3-60 518 632 7.1 50.0 0.8 2.6 .30 13.8 20† 13 6948HJD/HJE/HJF007(6 Tons)208/230-3-60 187 254 20.5 156.0 1.4 5.8 .57 38.8/38.8 45/45† 35/35 205/205460-3-60 414 508 9.6 70.0 0.6 2.6 .30 17.9 20† 17 94575-3-60 518 632 7.7 56.0 0.6 2.6 .30 14.3 20† 15 7948HJD/HJE/HJF008(71 /2 Tons)**208/230-3-60 187 254 12.4 88.0 1.4 7.5 .57 44.2/44.2 50/50† 46/46 247/247460-3-60 414 508 6.4 44.0 0.7 3.4 .30 21.9 25† 23 124575-3-60 518 632 4.8 34.0 0.7 3.4 .30 16.8 20† 17.5 9748HJD/HJE/HJF009(81 /2 Tons)**208/230-3-60 187 254 15.0 99.0 1.4 7.5 .57 50.1/50.1 60/60† 52/52 269/269460-3-60 414 508 8.2 49.5 0.7 3.4 .30 26.0 30† 27 135575-3-60 518 632 5.8 40.0 0.7 3.4 .30 19.1 25† 20 10948HJD/HJE/HJF012(10 Tons)**208/230-3-60 187 254 17.3 123.0 1.4 10.6 .57 58.3/58.3 70/70 61/61 341/341460-3-60 414 508 9.0 62.0 0.7 4.8 .30 29.2 35† 30 172575-3-60 518 632 7.1 50.0 0.7 4.8 .30 23.1 25† 24 13948HJD/HJE014(121 / 2 Tons)**208/230-3-60 187 254 19.0 156.0 1.4 15.0 .57 66.6/66.6 70/70 70/70 430/430460-3-60 414 508 9.0 70.0 0.7 7.4 .30 31.8 35† 33 199575-3-60 518 632 7.4 54.0 0.7 7.4 .30 25.9 30† 27 156FLA — Full Load AmpsHACR — Heating, Air Conditioning and RefrigerationIFM — Indoor (Evaporator) Fan MotorLRA — Locked Rotor AmpsMCA — Minimum Circuit AmpsMOCP — Maximum Overcurrent ProtectionNEC — National Electrical CodeOFM — Outdoor (Condenser) Fan MotorRLA — Rated Load AmpsUL — Underwriters’ LaboratoriesElectrical data (cont)