5InstallationProcedure InstallationPrecautions for InstallationNote) 1. About the specified liquid level range1) During cooling operation with the liquid level lower than the specified range, the moisture of the atmospherecondenses on the exposed part of the cooling coil, causing the condensate to be mixed into the liquid.If the liquid level further decreases, it results in cooling capacity deterioration, and also causes a fault of theunit.2) During heating operation the liquid level lower than the specified range, the heating element of the heater isexposed or discolored, or may emit burning smell. If the liquid level further decreases, the heater activates theoverheat protection device. This condition hinders normal operation, and also causes a fault of the unit.3) If the liquid level falls below the specified range due to liquid level fluctuations during operation, the liquid over-flows from the tank. To prevent the above 1) to 3) problems, be sure to maintain the liquid level within thespecified range.∗Mount a float switch to ensure that the liquid level in the tank is within the specified range.2. Give thorough consideration to the layout of the partitions and inlet/outlet piping for the installation tank, so thatthe low-temperature liquid that has been cooled with the OILCON unit can be uniformly mixed with the high-tem-perature liquid returned from the machine.Installation place and oil piping