Installation manual BRC1E52A713 4PW71264-1 – 10.20116. Field settings6-1 Press and hold Cancel button for4 seconds or longer.Service Settings menu isdisplayed.6-2 Select Field settings in theService Settings menu, andpress Menu/Enter button.Field settings screen isdisplayed.6-3 Highlight the mode, and selectdesired "Mode No." by using(Up/Down) button.6-4 In the case of setting per indoorunit during group control (WhenMode No. such as 20 , 21 ,22 , 23 , 25 are selected),highlight the unit No. and select"Indoor unit No." to be set byusing (Up/Down) button.(In the case of group setting, thisoperation is not needed.)In the case of individual settingper indoor unit, current settingsare displayed. And, SECONDCODE NO. " - " means nofunction.6-5 Highlight SECOND CODE NO. ofthe FIRST CODE NO. to bechanged, and select desired"SECOND CODE NO." by using(Up/Down) button. Multipleidentical mode number settingsare available.In the case of group setting, allof SECOND CODE NO. whichmay be set are displayed as" * ". " * " is changed toSECOND CODE NO. to be set.And, SECOND CODE NO. " - "means no function.6-1FanPress and hold Cancelbutton for 4 seconds orlonger during backlight lit.6-2Return SettingService SettingsTest OperationMaintenance ContactField SettingsDemandMin Setpoints DifferentialGroup Address1/3Press Menu/Enter button.In the case of individualsetting per indoor unitIn the case of groupsetting6-36-46-5Mode20Unit No01–005–––9–––2–006–––3–007–––Field settings0–014–––8–––Return Setting6-36-5 Mode10Unit No01–∗5–––9–––2–∗6–––3–∗7–––Field settings0–014–––8–––Return SettingPress Menu/Enter button.FIRST CODE (SW) NO.SECOND CODE NO.