21APPENDIX B ELECTRICAL DATAATTENTION INSTALLING PERSONNELUse only the heater kit specified for each model as dictated by the table above.UNIT HEATER KITMODEL NUMBERMINIMUM CFMDownshotMINIMUM CFMHorizontalEHK*-16 3000 3200EHK*-30 3000 3200EHK*-45 3000 3200EHK*-16 3400 3400EHK*-30 3400 3400EHK*-45 3400 3400EHK*-16 3500 3500EHK*-30 3500 3500EHK*-45 4000 4000EHK*-16 4000 4000EHK*-30 4300 4300EHK*-45 4500 4500MINIMUM AIR FLOW FOR ELECTRIC HEAT12.5 TON8.5 TON7.5 TON10 TONMIN MAX Qty RLA LRA Qty HP FLA HP FLA HP FLA208/230-60-3 187 253 2 13.1 83.1 2 1/4 1.40 BD STD STATIC 1.5 5.0 2 6.0460-60-3 414 506 2 6.1 41.0 2 1/4 0.80 BD STD STATIC 1.5 2.5 2 2.9575-60-3 518 633 2 4.4 33 2 1/4 0.55 BD STD STATIC 1.5 2.3 2 2.4208/230-60-3 187 253 2 13.1 83.1 2 1/4 1.40 BD STD STATIC 2.0 7.8 2 6.0460-60-3 414 506 2 6.1 41.0 2 1/4 0.80 BD STD STATIC 2.0 3.9 2 2.9575-60-3 518 633 2 4.4 33 2 1/4 0.55 BD STD STATIC 2.0 2.5 2 2.4208/230-60-3 187 253 2 14.5 98.0 2 1/4 1.40 BD STD STATIC 2.0 7.8 2 6.0460-60-3 414 506 2 6.3 55.0 2 1/4 0.80 BD STD STATIC 2.0 3.9 2 2.9575-60-3 518 633 2 6.0 41.0 2 1/4 0.55 BD STD STATIC 2.0 2.5 2 2.4208/230-60-3 187 253 2 16.0 110.0 2 1/3 2.40 BD STD STATIC 2.0 7.8 2.0 6.4460-60-3 414 506 2 7.8 52.0 2 1/3 1.20 BD STD STATIC 2.0 3.9 2.0 3.0575-60-3 518 633 2 6.4 38.9 2 1/3 0.67 BD STD STATIC 2.0 2.5 2.0 2.4208/230-60-3 187 253 2 22.4 149.0 2 1/3 2.40 BD STD STATIC 3.0 9.4 3.0 9.1460-60-3 414 506 2 10.6 75.0 2 1/3 1.20 BD STD STATIC 3.0 4.7 3.0 4.3575-60-3 518 633 2 7.70 54.0 2 1/3 0.67 BD STD STATIC 3.0 4.2 3.0 3.58.5 TON10 TON12.5 TONELECTRICAL DATAMODELS VOLTAGE(NAMEPLATE)VOLTAGELIMITATIONS COMPRESSOR (ea) OD FAN MOTORS(ea) ID MOTOR APPLID FAN MOTOR(ea)2 Speed ID FanMotor (ea)7.5 TONCOOLER7.5 TONHEATPUMP