TroubleshooTIngwww.DaikinApplied.com 19 IM 1229-1 • INTELLIGENT EQUIPMENTTroubleshooTIngGateway does not power up (LED does notilluminate)• Verify that power supply wires are properly installed onterminals— Rebel - Line (brown) conductor to terminal TB1-1 andthe Neutral (blue) conductor to terminal TB1-3— MicroTech III Maverick II - Line (brown) conductorto terminal TB1A-1, 2, 3, or 4 and Neutral (blue)conductor to terminal TB1A-5, 6, 7, 8, or 9• Verify 120V at appropriate terminals• Verify that power supply is properly connected to theGateway• Contact Daikin AppliedCell connection cannot be established• Check antenna connection to magnetic base• Check antenna connection to 3G/GPRS connection onGateway• Check signal strength through WebIF• Verify APN settings• Verify that neither a LAN or Wi-Fi connection has beenestablished• Confirm SIM card installation and recognition by gateway• Contact Daikin AppliedWi-Fi connection cannot be established• Check antenna connection to magnetic base• Check antenna connection to WLAN connection onGateway• Check signal strength through WebIF• Verify Wi-Fi IP addressing, ESSID, and login credentialsmatch customer supplied Wireless LAN requirements• Connect to Wi-Fi network and try to ping the Gateway’sWLAN IP address• Verify that neither a LAN or Cell connection has beenestablished• Contact Daikin AppliedLAN connection cannot be established• Confirm proper installation of USB to Ethernet adapter• Verify LED activity on USB to Ethernet adapter• Verify LAN addressing through Web IP• Connect to LAN and try to ping the Gateway’s LAN IPaddress• Verify that neither a Wi-Fi or Cell connection has beenestablished• Contact Daikin AppliedMicroTech III Data Not Showing Up In UserInterface• Confirm Ethernet cable is plugged into ‘ETH’ port onGateway• Confirm Ethernet cable is plugged into ‘TIP’ port onMicroTech III controller• Check for LED activity on Gateway’s ETH port• Verify IP address of Eth0 on the Gateway is 192 168 1 40• Verify IP address of the MicroTech III controller is192 168 1 42— On units with software versions later than2506017500 this can be done at the keypad• Contact Daikin Applied